178
H9 ASD Installation and Operation Manual
Speed 7 Operation Time
Program
Pattern Run
Operation Time
This parameter sets the run-time for
Preset Speed 7
.
This time is effective when used with
Group Speeds
and non-
Group Speeds
.
If the
Auto-Restart
function is activated, the search time required for the
Auto-
Restart
function will be subtracted from the
Operation Time
setting; resulting
in a shorter run time.
Direct Access Number — F546
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units —
F520
Setting
Speed 8 Operation Time
Program
Pattern Run
Operation Time
This parameter sets the run-time for
Preset Speed 8
.
This time is effective when used with
Group Speeds
and non-
Group Speeds
.
If the
Auto-Restart
function is activated, the search time required for the
Auto-
Restart
function will be subtracted from the
Operation Time
setting; resulting
in a shorter run time.
Direct Access Number — F547
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units —
F520
Setting
Speed 9 Operation Time
Program
Pattern Run
Operation Time
This parameter sets the run-time for
Preset Speed 9
This time is effective when used with
Group Speeds
and non-
Group Speeds
.
If the
Auto-Restart
function is activated, the search time required for the
Auto-
Restart
function will be subtracted from the
Operation Time
setting; resulting
in a shorter run time.
Direct Access Number — F548
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units —
F520
Setting
Speed 10 Operation Time
Program
Pattern Run
Operation Time
This parameter sets the run-time for
Preset Speed 10
This time is effective when used with
Group Speeds
and non-
Group Speeds
.
If the
Auto-Restart
function is activated, the search time required for the
Auto-
Restart
function will be subtracted from the
Operation Time
setting; resulting
in a shorter run time.
Direct Access Number — F549
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units —
F520
Setting
Speed 11 Operation Time
Program
Pattern Run
Operation Time
This parameter sets the run-time for
Preset Speed 11
This time is effective when used with
Group Speeds
and non-
Group Speeds
.
If the
Auto-Restart
function is activated, the search time required for the
Auto-
Restart
function will be subtracted from the
Operation Time
setting; resulting
in a shorter run time.
Direct Access Number — F550
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units —
F520
Setting
Speed 12 Operation Time
Program
Pattern Run
Operation Time
This parameter sets the run-time for
Preset Speed 12
This time is effective when used with
Group Speeds
and non-
Group Speeds
.
If the
Auto-Restart
function is activated, the search time required for the
Auto-
Restart
function will be subtracted from the
Operation Time
setting; resulting
in a shorter run time.
Direct Access Number — F551
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units —
F520
Setting
F546
F551