H9 ASD Installation and Operation Manual
71
Startup Wizard Parameter Requirements
The
Startup Wizard
queries the user for information on the I/O signal parameters, control, and the EOI
display settings of the ASD. The ASD may also be setup by directly accessing each of the startup settings
via the
Program
menu or the associated
Direct Access Numbers
(see the section titled
Direct Access
Parameter Information on pg. 76
).
Upon initial system power up, the
Startup Wizard
starts automatically. It may also be run from the
Program
menu after startup, if required. The user is queried to either (
1
)
Run Now
, (
2
)
Run Next Time
, or
(3)
Manually Configure
the ASD.
Select
Run Now
to start the
Startup Wizard
. The wizard will assist the user with the configuration of the
H9 Adjustable Speed Drive
using the user-input screens below starting with the
Voltage and Frequency
Rating of the Motor
.
Select
Run Next Time
to return to the
Program
menu. The system will default to the
Startup Wizard
on
the next power up.
Select
Manually Configure
to go to the
Finish
box. Click
Finish
to return the system to the
Frequency
Command
screen.
Voltage and Frequency Rating of the Motor
Motors are designed and manufactured to be operated within a specific voltage and frequency range. The
voltage and frequency specifications for a given motor may be found on the nameplate of the motor.
Highlight and click on the voltage and frequency of the motor being used.
Upper-Limit Frequency
This parameter sets the highest frequency that the ASD will accept as a frequency command or frequency
setpoint. The ASD may output frequencies higher than the
Upper-Limit Frequency
(but, lower than the
Maximum Frequency
) when operating in the
PID Control
mode,
Torque Control
mode, or the
Vector
Control
modes (sensorless or feedback).
Lower-Limit Frequency
This parameter sets the lowest frequency that the ASD will accept as a frequency command or frequency
setpoint. The ASD will output frequencies lower than the
Lower-Limit Frequency
when accelerating to
the lower-limit or decelerating to a stop. Frequencies below the
Lower-Limit
may be output when
operating in the
PID Control
mode,
Torque Control
mode, or the
Vector Control
modes (sensorless or
feedback).
Automatic Acceleration/Deceleration
When
Automatic ACC/DEC
is chosen, the ASD adjusts the acceleration and deceleration rates according
to the applied load. The minimum accel/decel time may be set using
F508
. The motor and the load must
be connected prior to selecting
Automatic Accel/Decel
.
Select
Manual
to allow the settings of
F009
and
F010
to control the accel/decel, respectively. The
acceleration and deceleration times range from 12.5% to 800% of the programmed values for the active
acceleration time.
Select
Automatic ACC Only
to allow for the acceleration rate to be controlled automatically only.
Acceleration Time
This parameter specifies the time in seconds for the output of the ASD to go from 0.0 Hz to the
Maximum
Frequency
for the
1 Acceleration
profile. The
Accel/Decel Pattern
may be set using
F502
.