H9 ASD Installation and Operation Manual
Regenerative Braking Torque Limit 1
Program
Torque
Torque Limit Settings
This parameter determines the source of the
Regenerative Torque Limit
control signal.
If
Setting
is selected, the value set at
F443
is used for this parameter.
Settings:
1 — V/I
2 — RR
3 — RX
4 —
F443
(Setting)
Direct Access Number — F442
Parameter Type —
Selection List
Factory Default —
F443
Setting
Changeable During Run —
Yes
Regenerative Braking Torque Limit 1 Level
Program
Torque
Torque Limit Settings
This parameter provides a value to be used as the
Regeneration Torque Limit
1
if
F443
is selected at parameter
F442
.
Set this parameter to
250%
to disable this function.
Direct Access Number — F443
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 249.9
Units — %
Power Running Torque Limit 2 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the positive torque upper-limit for the 2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F444
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Regenerative Braking Torque Limit 2 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the negative torque upper-limit for the 2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F445
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Power Running Torque Limit 3 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the positive torque upper-limit for the 3 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F446
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %