132
H9 ASD Installation and Operation Manual
Preset Speed 9
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 1001 and is
identified as
Preset Speed 9
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
(see
F018
for more information on
this parameter).
Direct Access Number — F288
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum —
Lower-Limit
(
F013
)
Maximum —
Upper-Limit
(
F012
)
Units — Hz
Preset Speed 10
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 1010 and is
identified as
Preset Speed 10
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
(see
F018
for more information on
this parameter).
Direct Access Number — F289
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum —
Lower-Limit
(
F013
)
Maximum —
Upper-Limit
(
F012
)
Units — Hz
Preset Speed 11
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 1011 and is
identified as
Preset Speed 11
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
(see
F018
for more information on
this parameter).
Direct Access Number — F290
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum —
Lower-Limit
(
F013
)
Maximum —
Upper-Limit
(
F012
)
Units — Hz
Preset Speed 12
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 1100 and is
identified as
Preset Speed 12
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
(see
F018
for more information on
this parameter).
Direct Access Number — F291
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum —
Lower-Limit
(
F013
)
Maximum —
Upper-Limit
(
F012
)
Units — Hz
Preset Speed 13
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 1101 and is
identified as
Preset Speed 13
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
(see
F018
for more information on
this parameter).
Direct Access Number — F292
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum —
Lower-Limit
(
F013
)
Maximum —
Upper-Limit
(
F012
)
Units — Hz
Preset Speed 14
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 1110 and is
identified as
Preset Speed 14
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
(see
F018
for more information on
this parameter).
Direct Access Number — F293
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum —
Lower-Limit
(
F013
)
Maximum —
Upper-Limit
(
F012
)
Units — Hz