H9 ASD Installation and Operation Manual
117
RX2 (AI1) Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RX2
(AI1) input terminal
when the
RX2
(AI1) terminal is used as the control input while operating in the
Speed Control
mode.
This parameter sets
RX2
(AI1)
Input Point 1 Frequency
and is the frequency
that is associated with the setting of
RX2
(AI1)
Input Point 1 Setting
when
operating in the
Speed Control
mode.
See
RX2
(AI1)
Input Point 1 Setting
(
F222
) for more information on this
setting.
Direct Access Number — F223
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
(
F011
)
Units — Hz
RX2 (AI1) Input Point 2 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RX2
(AI1) input terminal
when the
RX2
(AI1) terminal is used as the control input while operating in the
Speed Control
mode or the
Torque Control
mode.
This parameter sets the
RX2
(AI1) input level that is associated with
RX2
(AI1)
Input Point 2 Frequency
when operating in the
Speed
control mode or
is associated with the
RX2
(AI1)
Input Point 2 Rate
when operating in the
Torque Control
mode.
This value is entered as -100% to +100% of the
RX2
(AI1) input signal range.
See
RX2
(AI1)
Input Point 1 Setting
(
F222
) for more information on this
setting when used for
Speed
control.
See
RX2
(AI1)
Input Point 1 Rate
(
F226
) for more information on this setting
when used for
Torque Control
.
Direct Access Number — F224
Parameter Type —
Numerical
Factory Default —
+100
Changeable During Run —
Yes
Minimum — -100
Maximum — +100
Units — %
RX2 (AI1) Input Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RX2
(AI1) input terminal
when the
RX2
(AI1) terminal is used as the control input while operating in the
Speed Control
mode.
This parameter sets
RX2
(AI1)
Input Point 2 Frequency
and is the frequency
that is associated with the setting of
RX2
(AI1)
Input Point 2 Setting
when
operating in the
Speed Control
mode.
See
RX2
(AI1)
Input Point 1 Setting
(
F222
) for more information on this
setting.
Direct Access Number — F225
Parameter Type —
Numerical
Factory Default —
60.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
(
F011
)
Units — Hz
F223
F225