64
⎯
6 F 2 S 0 8 2 8
(
−
)
(+)
GRL150
BIa
BIb
External trip
A-phase
External trip
B-phase
BIa command
BIb command
Binary input setting
EXT_TRIP-A
1588
EXT_TRIP-B
1589
By PLC
By PLC
Figure 3.3.7.2 Binary Input Setting for CB Condition Monitoring
3.3.8 Failure
Alarms
When a failure is detected by the automatic supervision, it is followed with an LCD message, LED
indication, external alarm and event recording. Table 3.3.1 summarizes the supervision items and
alarms.
The LCD messages are shown on the "Auto-supervision" screen, which is displayed automatically
when a failure is detected or displayed by pressing the
VIEW
key. The event record messages are
shown on the "Event record" screen by opening the "Record" sub-menu.
The alarms are retained until the failure is recovered.
The alarms can be disabled collectively by setting the scheme switch [AMF] to "OFF". The setting
is used to block unnecessary alarms during commissioning, test or maintenance.
When the Watchdog Timer detects that the software is not running normally, LCD display and
event recording of the failure may not function normally.
Table 3.3.1 Supervision Items and Alarms
Supervision Item
LCD Message
LED
"IN SERVICE"
LED
"ALARM"
External
alarm
Alarm record Message
AC input imbalance monitoring
Err:CT
On/Off (2)
On
(4)
Relay fail or Relay fail-A (2)
A/D accuracy check
Err:A/D
Off
On
(4)
Relay fail
Memory monitoring
Err:SUM, Err:RAM,
Err:BRAM, Err:EEP
Off On
(4) Relay
fail
Watchdog Timer
----
Off
On
(4)
----
DC supply monitoring
Err:DC
Off
(3)
Off
Relay fail-A
Telecommunication monitoring
Err:COM
on
on
(5)
Com. fail
Sampling Synchronization
monitoring
Err:SYN
on
on
(4)
Sync. fail
Ready signal monitoring
Err:RDY
on
on
(5)
Term. rdy off
Disconnector monitoring
Err:DS
on
on
(5)
DS fail
Id monitoring
Err:Id
on/off (6)
On
(5)
Relay fail or Relay fail-A (2)
Trip circuit supervision
Err:TC
On
On
Off
Relay fail-A
CB state monitoring
Err:CB
On
On
Off
Relay fail-A
CB operating time monitoring
ALM:OP time
On
On
Off
Relay fail-A
Trip count alarm
ALM:TP COUNT
On
On
Off
Relay fail-A
∑
I
y
count alarm
ALM:
∑
IY
On On
Off Relay
fail-A
(1): Diverse messages are provided as expressed with "Err:---" in the table in Section 6.7.2.
(2): The LED is on when the scheme switch [CTSVEN] is set to "ALM" and off when set to "ALM &
Содержание GRL150-100 Series
Страница 149: ... 148 6 F 2 S 0 8 2 8 ...
Страница 150: ... 149 6 F 2 S 0 8 2 8 Appendix A Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 154: ... 153 6 F 2 S 0 8 2 8 Appendix B Signal List ...
Страница 180: ... 179 6 F 2 S 0 8 2 8 Appendix C Binary Output Default Setting List ...
Страница 182: ... 181 6 F 2 S 0 8 2 8 Appendix D Details of Relay Menu ...
Страница 195: ... 194 6 F 2 S 0 8 2 8 ...
Страница 196: ... 195 6 F 2 S 0 8 2 8 Appendix E Case Outline ...
Страница 199: ... 198 6 F 2 S 0 8 2 8 ...
Страница 200: ... 199 6 F 2 S 0 8 2 8 Appendix F Typical External Connections ...
Страница 223: ... 222 6 F 2 S 0 8 2 8 ...
Страница 228: ... 227 6 F 2 S 0 8 2 8 Appendix I Return Repair Form ...
Страница 232: ... 231 6 F 2 S 0 8 2 8 Appendix J Technical Data ...
Страница 238: ... 237 6 F 2 S 0 8 2 8 Appendix K Symbols Used in Scheme Logic ...
Страница 241: ... 240 6 F 2 S 0 8 2 8 ...
Страница 242: ... 241 6 F 2 S 0 8 2 8 Appendix L Inverse Time Characteristics ...
Страница 248: ... 247 6 F 2 S 0 8 2 8 Appendix M IEC60870 5 103 Interoperability ...
Страница 260: ... 259 6 F 2 S 0 8 2 8 Appendix N Resistor Box Option ...
Страница 263: ... 262 6 F 2 S 0 8 2 8 ...
Страница 264: ... 263 6 F 2 S 0 8 2 8 Appendix O Ordering ...
Страница 267: ......