65
⎯
6 F 2 S 0 8 2 8
BLK" (refer to Section 3.3.6). The message "Relay fail-A" is recorded when the scheme switch
[CTSVEN] is set to "ALM".
(3): Whether the LED is lit or not depends on the degree of the voltage drop.
(4): The binary output relay "FAIL" operates.
(5): The user-configurable binary output relays operate if assigned.
(6): The LED is on when the scheme switch [IDSVEN] is set to "ALM" and off when set to "ALM &
BLK".
The relationship between the LCD message and the location of the failure is shown in Table 6.7.1
in Section 6.7.2.
3.3.9 Trip
Blocking
When a failure is detected by the following supervision items, the trip function is blocked as long
as the failure exists, and is restored when the failure is removed.
•
A/D accuracy check
•
Memory
monitoring
•
Watchdog
Timer
•
Telecommunication channel monitoring
When a fault is detected by the AC input imbalance monitoring and Id monitoring, the scheme
switch [CTSVEN] setting can be used to determine if both tripping is blocked and an alarm is
output, or if only an alarm is output.
3.3.10 Setting
The setting element necessary for the automatic supervision and its setting range are shown in the
table below.
Element Range
Step Default Remarks
[CTSVEN] OFF/ALM&BLK/ALM
ALM&BLK Alarming and blocking or alarming only
[IDSVEN]
OFF/ALM&BLK/ALM
ALM&BLK
Alarming and blocking or alarming only
[TCSPEN] OFF/ON/OPT-ON
OFF
Trip circuit supervision
[CBSMEN]
OFF/ON
OFF
CB state monitoring
[TCAEN]
OFF/ON
OFF
Trip count alarm
[
∑
I
y
AEN]
OFF/ON
OFF
∑
I
y
count alarm
[OPTAEN]
OFF/ON
OFF
Operate time alarm
[FERAEN]
OFF/ON
OFF
Frame error rate alarm
DIFSV
50 – 100 %
1 %
50 %
DIFSV threshold setting (% of DIF setting)
TIDSV
0 – 60 s
1 s
10 s
DIFSV timer
TCALM
1 - 10000
1
10000
Trip count alarm threshold setting
∑
I
y
ALM
10 – 10000 E6
E6
10000
∑
I
y
alarm threshold setting
YVALUE
1.0 – 2.0
0.1
2.0
y value setting
OPTALM
100 – 5000 ms
10 ms
1000 ms
Operate time alarm threshold setting
CF-PER
1 – 60
1 s
10 s
CF period threshold
FERALM
0.0 – 50.0
0.1 %
20.0 %
Frame error rate alarm level
The scheme switch [CTSVEN] is set in the "Application" sub-menu. Other scheme switches are
set in the "Scheme sw" sub-menu.
Содержание GRL150-100 Series
Страница 149: ... 148 6 F 2 S 0 8 2 8 ...
Страница 150: ... 149 6 F 2 S 0 8 2 8 Appendix A Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 154: ... 153 6 F 2 S 0 8 2 8 Appendix B Signal List ...
Страница 180: ... 179 6 F 2 S 0 8 2 8 Appendix C Binary Output Default Setting List ...
Страница 182: ... 181 6 F 2 S 0 8 2 8 Appendix D Details of Relay Menu ...
Страница 195: ... 194 6 F 2 S 0 8 2 8 ...
Страница 196: ... 195 6 F 2 S 0 8 2 8 Appendix E Case Outline ...
Страница 199: ... 198 6 F 2 S 0 8 2 8 ...
Страница 200: ... 199 6 F 2 S 0 8 2 8 Appendix F Typical External Connections ...
Страница 223: ... 222 6 F 2 S 0 8 2 8 ...
Страница 228: ... 227 6 F 2 S 0 8 2 8 Appendix I Return Repair Form ...
Страница 232: ... 231 6 F 2 S 0 8 2 8 Appendix J Technical Data ...
Страница 238: ... 237 6 F 2 S 0 8 2 8 Appendix K Symbols Used in Scheme Logic ...
Страница 241: ... 240 6 F 2 S 0 8 2 8 ...
Страница 242: ... 241 6 F 2 S 0 8 2 8 Appendix L Inverse Time Characteristics ...
Страница 248: ... 247 6 F 2 S 0 8 2 8 Appendix M IEC60870 5 103 Interoperability ...
Страница 260: ... 259 6 F 2 S 0 8 2 8 Appendix N Resistor Box Option ...
Страница 263: ... 262 6 F 2 S 0 8 2 8 ...
Страница 264: ... 263 6 F 2 S 0 8 2 8 Appendix O Ordering ...
Страница 267: ......