Element Range
Step
Default
Remarks
SE1
0.025 – 0.125 A
(0.005 – 0.025 A)(*)
0.001 A
(0.001 A)
0.050 A
(0.010 A)
SEF1 threshold setting
TSE1M
(TMS)
0.010 – 1.500
0.001
1.000
SEF1 inverse time multiplier setting.
Required if [MSE1] = IEC, IEEE, US or
CON.
TSE1
0.00 – 300.00 s
0.01 s
1.00 s
SEF1 definite time setting. Required if
[MSE1] = DT.
TSE1R
0.0 – 300.0 s
0.1 s
0.0 s
SEF1 definite time delayed reset. Required
if [MSE1] = IEC or [SE1R] = DEF.
TSE1RM
(RTMS)
0.010 – 1.500
0.001
1.000
SEF1 dependent time delayed reset time
multiplier. Required if [SE1R] = DEP.
TSE12
0.00 – 300.00 s
0.01 s
1.00 s
SEF1 stage 2 definite time setting
SE2
0.025 – 0.125 A
(0.005 – 0.025 A)(*)
0.001 A
(0.001 A)
0.050 A
(0.010 A)
SEF2 threshold setting
TSE2
0.00 – 300.00 s
0.01 s
1.00 s
SEF2 definite time setting.
SE3
0.025 – 0.125 A
(0.005 – 0.025 A)(*)
0.001 A
(0.001 A)
0.050 A
(0.010 A)
SEF3 threshold setting
TSE3
0.00 – 300.00 s
0.01 s
1.00 s
SEF3 definite time setting.
SE4
0.025 – 0.125 A
(0.005 – 0.025 A)(*)
0.001 A
(0.001 A)
0.050 A
(0.010 A)
SEF4 threshold setting
TSE4
0.00 – 300.00 s
0.01 s
1.00 s
SEF4 definite time setting.
[SE1EN]
Off / On
Off
SEF1 Enable
[MSE1] DT/IEC/IEEE/US/CON DT
SEF1
characteristic
[MSE1C]
MSE1C-IEC
MSE1C-IEEE
MSE1C-US
NI / VI / EI / LTI
MI / VI / EI
CO2 / CO8
NI
MI
CO2
SEF1 inverse curve type.
Required if [MSE1] = IEC.
Required if [MSE1] = IEEE.
Required if [MSE1] = US.
[SE1R]
DEF / DEP
DEF
SEF1 reset characteristic. Required if
[MSE1] = IEEE or US.
[SE1S2]
Off / On
Off
SEF1 stage 2 timer enable
[SE2EN]
Off / On
Off
SEF2 Enable
[SE3EN]
Off / On
Off
SEF3 Enable
[SE4EN]
Off / On
Off
SEF4 Enable
[OC-ICD]
NA / BLK
NA
OC/EF/SEF blocked by irush current
(*) Current values shown in parenthesis are in the case of a 1 A rating. Other current values are in the
case of a 5 A rating.
Содержание GRL150-100 Series
Страница 149: ... 148 6 F 2 S 0 8 2 8 ...
Страница 150: ... 149 6 F 2 S 0 8 2 8 Appendix A Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 154: ... 153 6 F 2 S 0 8 2 8 Appendix B Signal List ...
Страница 180: ... 179 6 F 2 S 0 8 2 8 Appendix C Binary Output Default Setting List ...
Страница 182: ... 181 6 F 2 S 0 8 2 8 Appendix D Details of Relay Menu ...
Страница 195: ... 194 6 F 2 S 0 8 2 8 ...
Страница 196: ... 195 6 F 2 S 0 8 2 8 Appendix E Case Outline ...
Страница 199: ... 198 6 F 2 S 0 8 2 8 ...
Страница 200: ... 199 6 F 2 S 0 8 2 8 Appendix F Typical External Connections ...
Страница 223: ... 222 6 F 2 S 0 8 2 8 ...
Страница 228: ... 227 6 F 2 S 0 8 2 8 Appendix I Return Repair Form ...
Страница 232: ... 231 6 F 2 S 0 8 2 8 Appendix J Technical Data ...
Страница 238: ... 237 6 F 2 S 0 8 2 8 Appendix K Symbols Used in Scheme Logic ...
Страница 241: ... 240 6 F 2 S 0 8 2 8 ...
Страница 242: ... 241 6 F 2 S 0 8 2 8 Appendix L Inverse Time Characteristics ...
Страница 248: ... 247 6 F 2 S 0 8 2 8 Appendix M IEC60870 5 103 Interoperability ...
Страница 260: ... 259 6 F 2 S 0 8 2 8 Appendix N Resistor Box Option ...
Страница 263: ... 262 6 F 2 S 0 8 2 8 ...
Страница 264: ... 263 6 F 2 S 0 8 2 8 Appendix O Ordering ...
Страница 267: ......