66
*1 The TF / TSA / TOA sensors are equipped only with some types of indoor units. The data does not appear for other types.
*2 In the case of group connection, only the header indoor unit data can be displayed.
*3 The upper digit of CODE No. indicates the outdoor unit No.
*4 [(The upper digit of CODE No.) – 4] indicates the outdoor unit No.
1
✽
, 5
✽
... U1 outdoor unit (Center unit)
2
✽
, 6
✽
... U2 outdoor unit (terminal unit 1)
3
✽
, 7
✽
... U3 outdoor unit (terminal unit 2)
4
✽
, 8
✽
... U4 outdoor unit (terminal unit 3)
*5 Only CODE No. 5
✽
of U1 outdoor unit (Center unit) is displayed.
◆
LED display of circuit board
1.D501 (Red)
• Lights up when the power is turned on (Microcomputer works)
• Blinks at 1-second intervals (0.5-second): No EEPROM, or writing error
• Blinks at 10-second intervals (5-second): No DISP mode
• Blinks at 2-second intervals (1-second): Function change being set (EEPROM)
2.D403 (Red)
• Lights up (on hardware) when the power is supplied to the remote controller
3.D503 (Yellow): Indoor/Outdoor central control
• Lights up for the first half 5 seconds while communicating with a central control device
• Blinks for the second half 5 seconds at 0.2-second intervals (0.1-second) while communicating with
the outdoor unit
4.D504 (Green): Remote controller communication
• The group header unit lights up for the first half 5 seconds while communicating with the remote
controller
• Blinks for the second half 5 seconds at 0.2-second intervals (0.1-second) during communication
between group indoor header and follower
CODE No.
Data
Format
Unit
Remote controller display example
U1 U2 U3 U4
Individual
data 2 of
outdoor unit
*4
50 60 70
80 Rotation of compressor 1
×10
rps
[0642]=64.2 rps
51 61 71
81 Rotation of compressor 2
×10
rps
52 62 72
–
Rotation of compressor 3
×10
rps
53 63 73
83 Outdoor fan mode
×1
Mode
[0058]=Mode 58
54 64 74
84
Heat sink temperature of compressor
IPDU1
×1
°C
[0024]=24 °C
55 65 75
85
Heat sink temperature of compressor
IPDU2
×1
°C
56 66 76
–
Heat sink temperature of compressor
IPDU3
×1
°C
57 67 77
87 Heat sink temperature of outdoor fan IPDU
×1
°C
58
–
–
–
In heat/cool collecting control *5
0: Normal
1: In collecting control
[0010] = In heat collecting control
[0001] = In cool collecting control
59
–
–
–
Pressure release *5
0: Normal
1: In release control
[0010] = In pressure release control
5A
–
–
–
Discharge temperature release *5
[0001] = In discharge temperature
release control
5B
–
–
–
Terminal unit release (U2 / U3 / U4 outdoor
unit) *5
[0100] = In U2 outdoor unit release
control
[0010] = In U3 outdoor unit release
control
[0001] = In U4 outdoor unit release
control
5F 6F 7F 8F Horse power of outdoor unit
×1
HP
[0016]=16HP
Содержание A03-009
Страница 148: ...147 9 Exploded Diagram Service Parts List 9 1 1 way cassette type YH MMU AP0074YH AP0094YH AP0124YH ...
Страница 149: ...148 ...
Страница 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...
Страница 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Страница 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Страница 166: ...165 ...
Страница 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Страница 170: ...169 ...
Страница 173: ...172 MMD AP0564BH ...
Страница 174: ...173 ...
Страница 177: ...176 E Parts ...
Страница 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Страница 183: ...182 MMD AP0724H AP0964H ...
Страница 184: ...183 ...
Страница 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Страница 190: ...189 MMC AP0364H AP0484H ...
Страница 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Страница 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...
Страница 198: ...197 MMF AP0364H AP0484H AP0564H ...
Страница 199: ...198 MMF AP0364H AP0484H AP0564H ...
Страница 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Страница 206: ...205 MML AP0244BH ...
Страница 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Страница 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Страница 213: ...212 MML AP0244H ...
Страница 214: ...213 MML AP0244H ...