To check all the indoor unit addresses using an arbitrary wired remote controller.
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
(Execute it while the units are stopped.)
You can check indoor unit addresses and positions of the indoor units in a single refrigerant line.
When an outdoor unit is selected, the indoor unit numbers of the refrigerant line of the selected unit are indicated
one after another and the fan and louvers of the indicated indoor units are activated.
1
Push and hold the TIME
and
buttons at the same time for more than 4 seconds.
At first, the line 1 and CODE No.
(Address Change) are indicated on the LCD display. (Select
an outdoor unit.)
2
Push the
(left side of the button) and
buttons repeatedly to select a system
address.
3
Push the
button to confirm the system address selection.
• The address of an indoor unit connected to the selected refrigerant line is indicated on the LCD display and
its fan and louvers are activated.
4
Push the
button (left side of the button). Each time you push the button, the indoor unit
numbers of the selected refrigerant line are indicated one after another.
• Only the fan and louvers of the indicated indoor unit are activated.
◆
To select another system address
5
Push the
CL button to return to step
2
.
• After returning to step
2
, select another system address and check the indoor unit addresses of the line.
6
Push the
button to finish the procedure.
Содержание A03-009
Страница 148: ...147 9 Exploded Diagram Service Parts List 9 1 1 way cassette type YH MMU AP0074YH AP0094YH AP0124YH ...
Страница 149: ...148 ...
Страница 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...
Страница 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Страница 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Страница 166: ...165 ...
Страница 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Страница 170: ...169 ...
Страница 173: ...172 MMD AP0564BH ...
Страница 174: ...173 ...
Страница 177: ...176 E Parts ...
Страница 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Страница 183: ...182 MMD AP0724H AP0964H ...
Страница 184: ...183 ...
Страница 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Страница 190: ...189 MMC AP0364H AP0484H ...
Страница 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Страница 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...
Страница 198: ...197 MMF AP0364H AP0484H AP0564H ...
Страница 199: ...198 MMF AP0364H AP0484H AP0564H ...
Страница 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Страница 206: ...205 MML AP0244BH ...
Страница 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Страница 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Страница 213: ...212 MML AP0244H ...
Страница 214: ...213 MML AP0244H ...