Troubleshooting
6-1. Overview
(1) Before engaging in troubleshooting
(a) Applicable models
All Super Module Multi (SMMS, SHRM, Mini-SMMS, SMMS-i) models.
(Indoor units: MMO-APOOO, Outdoor units: MMY-MAPOOOO
, MCY-MAPOOOHT
)
(b) Tools and measuring devices required
• Screwdrivers (Philips, flat head), spanners, long-nose pliers, nipper, pin to push reset switch, etc.
• Multimeter, thermometer, pressure gauge, etc.
(c) Things to check prior to troubleshooting (behaviors listed below are normal)
(2) Troubleshooting procedure
When a fault occurs, proceed with troubleshooting in accordance with the procedure shown below.
NOTE
Rather than a genuine fault (see the List of Check Codes below), the problem could have been caused by a
microprocessor malfunction attributable to a poor quality of the power source or an external noise. Check for
possible noise sources, and shield the remote controller wiring and signal wires as necessary.
NO.
Behavior
Possible cause
1
A compressor would not start
• Could it just be the 3-minute delay period (3 minutes after compressor
shutdown)?
• Could it just be the air conditioner having gone thermo OFF?
• Could it just be the air conditioner operating in fan mode or put on the timer?
• Could it just be the system going through initial communication?
2
An indoor fan would not start
• Could it just be cold air discharge prevention control, which is part of
heating?
3
An outdoor fan would not start or would
change speed for no reason
• Could it just be cooling operation under low outside temperature
conditions?
• Could it just be defrosting operation?
4
An indoor fan would not stop
• Could it just be the elimination of residual heat being performed as part of
the air conditioner shutdown process after heating operation?
5
The air conditioner would not respond to a
start / stop command from a remote controller
• Could it just be the air conditioner operation under external or remote
controller?
Investigate check code displayed
on interface P.C. board of header
unit
Investigate check code
displayed on interface P.C.
board of relevant follower unit
Check fault site or
faulty part
Fault
"E28" error
Any other fault
Содержание A03-009
Страница 148: ...147 9 Exploded Diagram Service Parts List 9 1 1 way cassette type YH MMU AP0074YH AP0094YH AP0124YH ...
Страница 149: ...148 ...
Страница 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...
Страница 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Страница 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Страница 166: ...165 ...
Страница 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Страница 170: ...169 ...
Страница 173: ...172 MMD AP0564BH ...
Страница 174: ...173 ...
Страница 177: ...176 E Parts ...
Страница 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Страница 183: ...182 MMD AP0724H AP0964H ...
Страница 184: ...183 ...
Страница 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Страница 190: ...189 MMC AP0364H AP0484H ...
Страница 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Страница 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...
Страница 198: ...197 MMF AP0364H AP0484H AP0564H ...
Страница 199: ...198 MMF AP0364H AP0484H AP0564H ...
Страница 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Страница 206: ...205 MML AP0244BH ...
Страница 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Страница 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Страница 213: ...212 MML AP0244H ...
Страница 214: ...213 MML AP0244H ...