100
Procedure 1: reading setting data from EEPROM
(Read the setting data from EEPROM, including both the factory settings and any modifications made to them on
site.)
1
Push the
+
+
buttons simultaneously and hold for at least 4 seconds. (This number
corresponds to the same number shown on the Remote Controller Operation Diagram.)
* In the case of group control, the unit No. displayed first is the indoor unit No. of the header unit.
At the same time, the CODE No. (DN code) 10 is displayed, and the fan of the selected indoor unit comes
on, with the louver swinging, depending on the model.
2
Each time the
button is pushed, one of the indoor unit No. under group control is
displayed in turn.
* The fan of the selected indoor unit comes on, with the louvers swinging, depending on the model.
3
The
button allows you to move the CODE No. (DN code) up / down by one place.
4
First, change the CODE No. (DN code) from 10 to 01. (To set filter sign lighting time)
Jot down the setting data displayed.
5
Change the CODE No. (DN code) using the
button.
Again, jot down the setting data displayed.
6
Repeat step
5
until all the setting data has been jotted down. (See the CODE No. list.)
* CODE No. (DN code) go from 01 to FF with a few gaps along the way.
7
When finished, push the
button to bring the system back to normal off state.
(It takes the system about 1 minute to become responsive to remote controller operation.)
CODE No. (DN code) necessary at minimum
The type and capacity of the indoor unit are necessary for fan speed setting.
DN
Contents
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor address
14
Group address
Remote controller operation diagram
Содержание A03-009
Страница 148: ...147 9 Exploded Diagram Service Parts List 9 1 1 way cassette type YH MMU AP0074YH AP0094YH AP0124YH ...
Страница 149: ...148 ...
Страница 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...
Страница 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Страница 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Страница 166: ...165 ...
Страница 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Страница 170: ...169 ...
Страница 173: ...172 MMD AP0564BH ...
Страница 174: ...173 ...
Страница 177: ...176 E Parts ...
Страница 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Страница 183: ...182 MMD AP0724H AP0964H ...
Страница 184: ...183 ...
Страница 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Страница 190: ...189 MMC AP0364H AP0484H ...
Страница 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Страница 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...
Страница 198: ...197 MMF AP0364H AP0484H AP0564H ...
Страница 199: ...198 MMF AP0364H AP0484H AP0564H ...
Страница 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Страница 206: ...205 MML AP0244BH ...
Страница 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Страница 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Страница 213: ...212 MML AP0244H ...
Страница 214: ...213 MML AP0244H ...