Ventilating fan control from remote controller
[Function]
• The start / stop operation can be operated from the wired remote controller when air to air heat exchanger
or ventilating fan is installed in the system.
• The fan can be operated even if the indoor unit is not operating.
• Use a fan which can receive the no-voltage A contact as an outside input signal.
• In a group control, the units are collectively operated and they can not be individually operated.
1. Operation
Handle a wired remote controller in the following procedure.
* Use the wired remote controller during stop of the system.
* Be sure to set up the wired remote controller to the header unit. (Same in group control)
* In a group control, if the wired remote controller is set up to the header unit, both header and follower units
are simultaneously operable.
1
Push concurrently
+
+
buttons for 4 seconds or more.
The unit No. displayed firstly indicates the header indoor unit address in the group control.
In this time, the fan of the selected indoor unit turns on.
2
Every pushing
button, the indoor unit numbers in group control are displayed
successively.
In this time, the fan of the selected indoor unit only turns on.
3
Using the setup temp
or
button, specify the CODE No.
31
.
4
Using the timer time
or
button, select the SET DATA. (At shipment:
)
The setup data are as follows:
5
Push
button. (OK if display goes on.)
• To change the selected indoor unit, go to the procedure
2
).
• To change the item to be set up, go to the procedure
3
).
6
Pushing
returns the status to the usual stop status.
2. Wiring
SET DATA
Handling of operation of air to air heat exchanger or ventilating fan
Unavailable (At shipment)
Available
Compact 4-way Cassette type
1-way Cassette type (SH)
Concealed Duct Standard type
Slim Duct type
Ceiling type
Corresponds up to a relay in which rated current of the
operation coil is approx. 75 mA
Other type models:
Correspond up to a relay in which rated current of the
operation coil is approx. 16 mA (Does not
correspond to a terminal block type relay on the market.)
Relay (DC12 V, procured locally)
Corresponds to the relay up to one that
the rated current of the operation coil is
approx. 75 mA
Outside control
input of fan
To terminal
Note) Determine the cable length between the indoor
control P.C. board and the relay within 2 m.
model :
Indoor control
P.C. board
Содержание A03-009
Страница 148: ...147 9 Exploded Diagram Service Parts List 9 1 1 way cassette type YH MMU AP0074YH AP0094YH AP0124YH ...
Страница 149: ...148 ...
Страница 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...
Страница 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Страница 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Страница 166: ...165 ...
Страница 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Страница 170: ...169 ...
Страница 173: ...172 MMD AP0564BH ...
Страница 174: ...173 ...
Страница 177: ...176 E Parts ...
Страница 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Страница 183: ...182 MMD AP0724H AP0964H ...
Страница 184: ...183 ...
Страница 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Страница 190: ...189 MMC AP0364H AP0484H ...
Страница 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Страница 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...
Страница 198: ...197 MMF AP0364H AP0484H AP0564H ...
Страница 199: ...198 MMF AP0364H AP0484H AP0564H ...
Страница 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Страница 206: ...205 MML AP0244BH ...
Страница 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Страница 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Страница 213: ...212 MML AP0244H ...
Страница 214: ...213 MML AP0244H ...