TAD MS 400V / 230V
Error
State
Diagnosed cause
F20
Door responds only to
dead man's control
for closing
Testing of photoelectric sensor
has failed. Check photoelectric
sensor.
F21
Brief operational in-
terruption
Door movement exceeded time
value detected (90 sec). Check
door for ease of motion or block-
age. Check end positions.
F22
Hydraulic motor
switches off
Runtime limitation of motor pump,
faulty operation or defective but-
ton.
F23
No response
Electronic door lock EDL100 is
not responding. Check wiring.
Locking bolt is jammed, check
locking bolt for ease of motion.
Do not apply oil or grease to door
locking.
F24
No response to start
command
No connection to the DES. Check
motor connection cable and DES.
F25
No response
Internal test or membrane keypad
erroneous. Exchange membrane
keypad or control.
F26
No response
Internal test external button /
switch failed.
F27
Drive blocked
Check door mechanics / check
phases, motor connection cable.
F28
No response to start
command
Voltage supply error. Check
mains connection. Check peri-
pherals for short circuit.
F29
Motor rotates in incor-
rect direction.
Mains phases have been inver-
ted. Correct or re-adjust.
F30
Door only runs in
dead man mode for
closing
Return from pulsed operation to
dead man mode. Check closing
edge safety device and photo-
electric sensor.
F31
Door neither opens
nor closes
Button actuated. Continuous
pulse pending. Check external
control devices (J1).
F32
Door neither opens
nor closes
Spring fracture detection has
tripped. Check springs, replace, if
necessary. When the springs
have been replaced, the
door end position must be re-ad-
justed.
F33
Door stops during the
opening process
Opening force limitation has
tripped. Door can only be closed
in dead man mode. Eliminate
sluggishness or blockage of the
door. Check springs. Eliminate
the cause of the excessive force,
then open and close the door.
F34
Door neither opens
nor closes
Duty cycle exceeded. Wait and let
motor cool down.
F35
Door neither opens
nor closes
Speed monitor has tripped.
Check DU setting.
F40
Extended control
does not respond
24 V failed. Check connections
on extended control.
F41
Extended control
does not respond
Error occurred during self-testing.
Replace extended control.
F43
Extended control
does not respond
No connection.
F45
RadioBand, wireless
closing edge
Module is not available, attach.
F46
RadioBand, wireless
closing edge
Replace battery.
Error
State
Diagnosed cause
F71
Erroneous wicket
door contact. Door
neither opens nor
closes
Check contact resistances. Check
assembly of wicket door, open
and close wicket door, check as-
sembly.
F72
Door neither opens
nor closes
Short circuit detected in the safety
circuit wicket door contact / slack
rope switch J4.1/2. Check cables
for short circuit, eliminate short
circuit.
F73
Door neither opens
nor closes. Testing of
input J4.1/2 failed
Switch control on and off. If ne-
cessary, replace control.
F74
Door neither opens
nor closes. Testing of
input J4.3/4 failed
Switch control on and off. If ne-
cessary, replace control.
F75
Door neither opens
nor closes. Output
voltage J4 erroneous
Switch control on and off. Check
closing edge safety device, door
connection box for short circuit.
Check terminal assignment.
F76
Door neither opens
nor closes. Invalid
sensors J4.1/2 detec-
ted
Check resistors. Check sensors.
F77
Door neither opens
nor closes. Invalid
sensors J4.3/4 detec-
ted
Check resistors. Check sensors.
F78
Drive blocks in end
position CLOSE
Check spring tension, check door
mechanics, check CLOSE end
position.
L
The access to the
menu was inhibited
by the authorized
specialist dealer.
Contact specialist dealer. Menu
can only be unlocked by means
of the service tool.
Lo
Control has been in-
hibited.
Contact specialist dealer. Menu
can only be unlocked by means
of the service tool.
U
The access to the
menu was unlocked
by the authorized
specialist dealer.
If the safety circuit is
interrupted, the warn-
ing indicator is illu-
minated, see
troubleshooting.
The warning indicator
flashes
upon switch-
ing the main switch
on and off.
The restart lock is active. Press
the
button or RETURN.