172-65720MA-00 (FJ32-X+BD2) 22 Dec 2021
8
Installation
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or malfunctions
that may lead to serious accidents. Local regulations may restrict the use of this
product to below the conditions quoted.
Take measures to prevent people from coming into direct contact with product
outlets.
Failure to do so may result in burns or other injury from the discharge of fluids.
Installation, inspection, maintenance, repairs, disassembly, adjustment and valve
opening/closing should be carried out only by trained maintenance personnel.
1. Before installation, be sure to remove all protective seals.
2. Before installing the product, blow out the inlet piping to remove any piping scraps,
dirt and oil. Close the inlet valve after blowdown.
3. Install the connector body so that the arrow is pointing in the direction of flow.
4. The connector body has no restrictions on installation orientation except for the
following conditions: the flange face (for connecting to the trap unit) must be in the
vertical plane, and the trap unit must be installed with the nameplate facing upwards.
5. The trap unit must be inclined no more than 5° horizontally and front-to-back.
6. Install a condensate outlet valve and outlet piping.
7. Open the inlet and outlet valves and ensure that the product functions properly.
If there is a problem, determine the cause using the “Troubleshooting” section in this
manual.
Tolerance Angle for Installation: 5°
Install with the arrow on the connector body pointing in the direction
of flow, with the flange (for connecting to the trap unit) in the vertical
plane and the trap unit with the nameplate facing upwards.
CAUTION