172-65720MA-00 (FJ32-X+BD2) 22 Dec 2021
22
No.
Part Name
Torque:
N∙m (
lbf·ft)
Distance Across Flats: mm (in)
1
Gland Retainer Nut
30
(22)
22
(
7
/
8
)
2
Gland Case
30
(22)
19
(
3
/
4
)
3
Gland Packing
4
Needle Valve
5
Gasket
6
Snap Ring
Operating Instructions for Lock Release Valve
1. When shipped from the factory, the needle valve is in the closed position.
2. To operate the needle valve, insert a flat-head screwdriver into the slot on the top of
the needle valve and:
Open Valve: slowly turn counterclockwise. (Do not continue turning the needle
valve past the point at which the snap ring contacts the bottom of the gland
case.)
See the table below to determine the amount of steam discharge
Close Valve: slowly turn clockwise. (Do not continue turning the needle valve
past the point at which it stops.)
3. If steam should leak from the gland retainer nut or gland case, it can be stopped by
further tightening the gland retainer nut. (Do not over tighten, otherwise the needle
valve may seize and become unworkable)
Steam Discharge
Differential Pressure (MPa)
Di
s
c
ha
rge
Cap
ac
ity
(
k
g/h
)
Differential Pressure (kg/cm
2
)
More than 1.5 turns
1 Turn
¾ Turns
½ Turn
¼ Turn
Number of turns from
full-closed position
Differential Pressure (psi)
More than 1.5 turns
1 Turn
¾ Turns
½ Turn
¼ Turn
Number of turns from
full-closed position
Di
s
c
ha
rge
Cap
ac
ity
(
lb
/h)