172-65188M-08 (
M-COS 3,16,21
Pressure Reducing Valve) 24 Jun 2015
5
Controller
Model
MC-2
Pressure Display Function
Yes
(select between displays of measured pressure and
upper pressure)
Pressure Upper Limit Setting
Function
Setting is possible
Power Source Voltage
100/110 VAC
±
10% or 200/220 VAC
±
10% (50/60 H
Z
)
Power
Consumption
While motor is
stopped
7 VA
While motor is
in operation
(TYP.) 65 VA (MAX.) 75 VA
Withstand Voltage
Between power terminal and ground terminal:
1800 VAC (60 H
Z
) for 1 second
Insulation Resistance
Between ground terminal and each terminal:
Min. 100 M
Ω (500 VDC)
O
per
at
ing
C
ondi
ti
ons
Ambient Temperature
0
–
50 °C
Ambient Humidity
5
–
90% RH (without dew, indoor use)
Vibration Resistance
Max. 0.5 G
Dimensions (Unit: mm)
93 (W)
×
184 (H)
×
73 (D)
Weight
1.1 kg
Installation
Wall mounting (M5 screw x 4)
Material/Coating
Steel plate/black melamine
P
res
s
ur
e
Indi
c
at
ion
Indication Range
0
–
1999 kPaG
Indication Accuracy
±
0.5%F.S.
Pressure Sensor
Standard type
Allowable Pressure
Setting Range
0 – 1999 kPaG
Pressure Sensor
Standard type
Model
M-COS-3
M-COS-16
/
M-COS-21
Pressure Measurement Range
0 – 0.5 MPaG (500 kPaG) type
0 – 2.0 MPaG type
0 – 0.5 MPaG (500 kPaG) type
*1
Signal Output
4 – 20 mADC (load resistance 250
Ω/15 VDC)
Measurement Accuracy
±
0.3%F.S.
Temperature Drift
±
0.02%F.S/°C
Maximum Allowable Pressure
2 times the maximum value of the measurement range
Ambient Temperature
−
40 –
+
85 °C (Sensor must not come into contact with dew)
Water Resistance
JIS Rain-proof type
Material for Wetted Parts
AISI 316 / DIN W. No. 1.4401
Connection Thread
G(PF)
3
/
8
Weight
Approx. 400 g
Accessories
Siphon Tube
(connector screw for piping installation end: R(PT)
3
/
8
)
*1
When the secondary pressure is 0.03 MPaG or less, choose a 0
–
0.5 MPaG (500 kPaG)