172-65188M-08 (
M-COS 3,16,21
Pressure Reducing Valve) 24 Jun 2015
12
4. Spacer Installation
If spacing adjustment is
necessary to accommodate
installation, install a spacer on
the outlet flange. The spacer
should consist of a spacer,
gaskets, bolts and nuts. Fit
gaskets to both sides of the
spacer between the
M-COS
outlet and the pipe flange.
Fasten with bolts and nuts.
Correct spacer
location
Correct spacer
location
5. Piping Support
Install the
M-COS
, paying
attention to avoid excessive
load, bending and vibration.
Support the inlet and outlet
pipes securely.
6. Maintenance Space
150
100
100
100
400
400
Approx.
300
Leave sufficient space for
maintenance, inspection and repair.
(Unit: mm)
7. Trap Outlet Piping
For ease of maintenance, installation
of a union connection is
recommended for the trap outlet pipe.
Connect the outlet pipe to a
condensate return line, or extend it to
a trench. In the case of the latter,
make sure the end of the pipe is
above the waterline.
(Dirt and water may otherwise be
sucked up by the vacuum formed
during trap closure and system
shutdown.)
Small hole