172-65188M-08 (
M-COS 3,16,21
Pressure Reducing Valve) 24 Jun 2015
11
Installation
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
Use hoisting equipment for heavy objects (weighing approximately
20 kg or more). Failure to do so may result in back strain or other injury if
the object should fall.
CAUTION
Take measures to prevent people from coming into direct contact with
product outlets. Failure to do so may result in burns or other injury from
the discharge of fluids.
CAUTION
Make sure the power supply switch is OFF before carrying out work on
the wiring or inspections involving disassembly.
If such work is carried out with the power on, there is a danger that
equipment may malfunction or electric shock may occur, leading to
injury or other accidents.
CAUTION
Make sure that wiring work requiring a special license is carried out by
qualified personnel.
If carried out by unqualified personnel, overheating or short circuits
leading to injury, fires, damage or other accidents may occur.
CAUTION
When using this product, NEVER stand close to, or leave tools anywhere
near moving parts, such as the shaft.
Contact with moving parts or objects becoming caught in moving parts
could lead to injury, damage or other accidents.
CAUTION
Installation, inspection, maintenance, repairs, disassembly, adjustment and valve
opening/closing should be carried out only by trained maintenance personnel.
1. Blowdown
Before installing the
M-COS
, be
sure to blow down all piping
thoroughly. If this is not possible,
perform a blowdown using the
bypass valve.
Blowdown is especially important
for newly installed piping or after
the system has been shut down
for a long period of time.
Open
Closed
Closed
Blowdown using bypass valve
M-COS
2. Removing Seal and Cap
Before installation, be sure to remove all protective
seals and caps.
(Found in 3 locations, on the product inlet and outlets.)
3. Installation Angle
Install the
M-COS
vertically, so that the
arrow mark on the body points horizontally
in the direction of steam flow.
Allowable inclination is 10 degrees in the
fore-aft direction and 15 degrees in the
plane perpendicular to the steam flow line.