19
NV10P - Manual - 01 - 2015
TECHNICAL DATA
Ten minutes overvoltage - 59Uavg
[1]
for inductive VTs versions
Common confi guration:
Operating logic (
Logic59Uavg
)
AND/OR
Uavg> Element
Defi nite time
First threshold defi nite time (
U
avg
>
def
)
0.50...1.50
U
n
(step 0.01
U
n
)
Time delay (
t
Uavg
>
def
)
0...1000 s (step 1 s)
Pickup time
according to the reference conditions
[2]
Pickup
accuracy ±
1% ±
1%
U
n
Time delay accuracy
[3]
5% ±
3 s
Ten minutes overvoltage - 59Uavg
[1]
for electronic sensor versions
Common confi guration:
Voltage measurement type (
Utype59Uavg
)
U
ph-ph
/
U
ph-n
Operating logic (
Logic59Uavg
)
AND/OR
Uavg> Element
Defi nite time
First threshold defi nite time (
U
avg
>
def
)
0.50...1.50
U
n
(step 0.01
U
n
/
E
n
)
Time delay (
t
Uavg
>
def
)
0...1000 s (step 1 s)
Pickup time
according to the reference conditions
[2]
Pickup
accuracy ±
1% ±
1%
U
n
/
E
n
Time delay accuracy
[3]
5% ±
3 s
Residual overvoltage - 59N for inductive VTs versions
Common confi guration:
Residual voltage measurement type for 59N - direct/calculated (
3
V
o
Type59N
)
U
E
/
U
EC
Operation from 74VT external (
74VText
59N)
OFF
/Block
U
E
>
Element
U
> Curve type (
U
>
Curve
)
DEFINITE/INVERSE
[4]
U
E
>
Reset time delay
(
t
UE>RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Defi nite time
59N First threshold defi nite time (
U
E
>
def
) 0.01...0.70
U
En
(step 0.01
U
En
)
U
E
>
def
Operating time (
t
UE
>
def
)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Inverse time
59N First threshold inverse time (
U
E
>
inv
) 0.01...0.50
U
En
(step 0.01
U
En
)
U
E
>
inv
Operating time (
t
UE
>
inv
)
0.10...100.0
s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Element
U
E
>>
U
E
>>
Reset time delay (
t
UE>>RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Defi nite time
59N Second threshold defi nite time (
U
E
>>
def
)
0.01...0.70
U
En
(step 0.01
U
En
)
U
E
>>
def
Operating time (
t
UE
>>
def
)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
U
E
>>
Reduced Operating time
(
t
cUE
>>
def
)
0.07...10.00 s (step 0.01 s)
t
cUE
>> Activation time (
t
atcUE
>>) 1...60 s (step 1 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.04 s
Overshoot
time
0.03
s
Pickup
accuracy ±
1% ±
1%
U
En
Operate
time
accuracy
5%
or
±
10 ms
Note 1 The function is based on the measurement of the mean of the three phase voltages of 10 minutes with update every three seconds
Note 2 The pickup time depends on the initial and fi nal value of the input voltage; e.g. with a setting of threshold equal to 1.10 Un:
- with initial value 0 and fi nal value 1.1 Uavg> def (1.1x1.1 = 1.21 Un) the pickup time is 498 s
- with initial value 0.9 Uavg>def (0.9x1.1 = 0.99 Un) and fi nal value 1.1 Uavg>def (1.1x1.1 = 1.21 Un) the pickup time is 285 s
Note 3 Since the aggregate value is updated every 3 s, times are only meaningful in multiples of 3 s
Note 4 The mathematical formula for INVERSE curve is t= (0.5 ∙
t
UE
>
inv
) / [(
U
E
/
U
E
>
inv
) - 1]
t = operating time (in seconds)
t
UE
>
inv
= operating time setting (in seconds)
U
E
= residual input voltage (direct or calculated)
U
E
>
inv
= threshold setting