169
NV10P - Manual - 01 - 2015
APPENDIX
Description
Parameter Unit
Setting range
U1< Trip relays
U1<TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U1< Start LEDs
U1<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
U1< Trip LEDs
U1<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
27V1 First threshold defi nite time
State
OFF | ON
Pickup value
Un
0.05 ... 1.10 step = 0.01
U1<def Operating time
Value
s
0.07 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Overvoltage - 59
Common confi guration
59 Operating logic
Logic59
OR | AND
U> Element
Setpoints
U> Enable
U> Enable
OFF | ON
U> Curve type
U>Curve
INVERSE | DEFINITE
U> Logical block
U>BLK1
OFF | ON
U> Breaker failure
U>BF
OFF | ON
U> Disabling by CB_OPEN
U>disbyCB_
OPEN
OFF | ON
U> Start relays
U>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U> Trip relays
U>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U> Start LEDs
U>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
U> Trip LEDs
U>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
59 First threshold defi nite time
State
OFF | ON
Pickup value
Un
0.50 ... 1.50 step = 0.01
U>def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Inverse time
59 First threshold inverse time
State
OFF | ON
Pickup value
Un
0.50 ... 1.50 step = 0.01
U>inv Operating time
tU>inv
s
0.10 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
U>> Element
Setpoints
U>> Logical block
U>>BLK1
OFF | ON
U>> Breaker failure
U>>BF
OFF | ON
U> Disabling by U>> start
U>disbyU>>
OFF | ON
U>> Disabling by CB_OPEN
U>>disbyCB_
OPEN
OFF | ON
U>> Start relays
U>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U>> Trip relays
U>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U>> Start LEDs
U>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
U>> Trip LEDs
U>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10