APPENDIX
Description
Parameter Unit
Setting range
Loop 3 Measure assigned
Loop3-Mis
Frequency | UL1 | UL2 | UL3 | UL1avg | UL2avg |
UL3avg | UE | UL | UEC | U1 | U2 | PLC | None
Loop 3 Output range
Loop3-Range
0-5 mA | 0-20 mA | 4-20 mA
Loop 3 Output type
Loop3-Type
Unipolar | Bipolar
Loop 3 Nominal multiplier
Loop3-M
0.01 ... 100.00 step = 0.01
Loop 3 Terminals polarity
Loop3-Polarity
Normal | Reverse
Current loop 4
Loop 4 Measure assigned
Loop4-Mis
Frequency | UL1 | UL2 | UL3 | UL1avg | UL2avg |
UL3avg | UE | UL | UEC | U1 | U2 | PLC | None
Loop 4 Output range
Loop4-Range
0-5 mA | 0-20 mA | 4-20 mA
Loop 4 Output type
Loop4-Type
Unipolar | Bipolar
Loop 4 Nominal multiplier
Loop4-M
0.01 ... 100.00 step = 0.01
Loop 4 Terminals polarity
Loop4-Polarity
Normal | Reverse
Self-test Relay
MINOR Fail alarm
NO | YES
Self-test relay
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
MMI
Modules data visualization
Assigned modules | All modules
Profi le selection
Active profi le
A | B | By INPUT
Profi le A
Thermal protection with RTD thermometric probes - 26
PT1 Probe
ThAL1 Alarm
ThAL1 Enable
ThAL1 Enable
OFF | ON
26 PT1 Alarm threshold
ThAL1
^C
0 ... 200 step = 1
ThAL1 Operating time
Value
s
0 ... 100 step = 1
ThAL1 Alarm relays
ThAL1-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
ThAL1 Alarm LEDs
ThAL1-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Th>1 Trip
Th>1 Enable
Th>1 Enable
OFF | ON
26 PT1 Trip threshold
Th>1
^C
0 ... 200 step = 1
Th>1 Operating time
Value
s
0 ... 100 step = 1
Th>1 Breaker failure
Th>1BF
OFF | ON
Th>1 Trip relays
Th>1-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Th>1 Trip LEDs
Th>1-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
PT2 Probe
ThAL2 Alarm
ThAL2 Enable
ThAL2 Enable
OFF | ON
26 PT2 Alarm threshold
ThAL2
^C
0 ... 200 step = 1
ThAL2 Operating time
Value
s
0 ... 100 step = 1
ThAL2 Alarm relays
ThAL2-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
ThAL2 Alarm LEDs
ThAL2-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Th>2 Trip
Th>2 Enable
Th>2 Enable
OFF | ON
26 PT2 Trip threshold
Th>2
^C
0 ... 200 step = 1
Th>2 Operating time
Value
s
0 ... 100 step = 1