![Thytronic NV10P Скачать руководство пользователя страница 158](http://html1.mh-extra.com/html/thytronic/nv10p/nv10p_manual_1113997158.webp)
158
158
NV10P - Manual - 01 - 2015
APPENDIX
Description
Parameter Unit
Setting range
U>> Logical block
U>>BLK1
OFF | ON
U>> Breaker failure
U>>BF
OFF | ON
U> Disabling by U>> start
U>disbyU>>
OFF | ON
U>> Disabling by CB_OPEN
U>>disbyCB_
OPEN
OFF | ON
U>> Start relays
U>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U>> Trip relays
U>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U>> Start LEDs
U>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
U>> Trip LEDs
U>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
59 Second threshold defi nite time
State
OFF | ON
Pickup value
Un
0.50 ... 1.50 step = 0.01
U>>def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Average overvoltage - 59Uavg
Common confi guration
59Uavg Operating logic
Logic59Uavg
OR | AND
Uavg> Element
Setpoints
Uavg> Enable
Uavg> Enable
OFF | ON
Uavg> Logical block
Uavg>BLK1
OFF | ON
Uavg> Breaker failure
Uavg>BF
OFF | ON
Uavg> Disabling by CB_OPEN
Uavg>disbyCB_
OPEN
OFF | ON
Uavg> Start relays
Uavg>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Uavg> Trip relays
Uavg>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Uavg> Start LEDs
Uavg>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Uavg> Trip LEDs
Uavg>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
59Uavg First threshold defi nite time
State
OFF | ON
Pickup value
Un
0.50 ... 1.50 step = 0.01
Uavg>def Delay time
Value
s
0 ... 1000 step = 1
Residual overvoltage - 59N
Common confi guration
Residual voltage measurement type for 59N - direct/cal-
culated
3VoType59N
UE | UEC
59N Operation from 74VT external
74VText59N
OFF | Block
UE> Element
Setpoints
UE> Enable
UE> Enable
OFF | ON
UE> Curve type
UE>Curve
INVERSE | DEFINITE
UE> Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE> Logical block
UE>BLK1
OFF | ON
UE> Breaker failure
UE>BF
OFF | ON