24
DTM
(DISTRIBUTED TEMPERATURE MODULE)
The DTM is a DIN rail mountable six RTD sensor input module
which links the field RTD wiring to the DCM module via CANBus.
Any RTD sensor may be mapped to any heater circuit on the
CANBus network.
DTM
PRODUCT FEATURES
• Up to six RTD sensors that can be independently addressed to
one or more heat trace circuits
• DIN rail mountable
• Conformal coated printed circuit board for use in panels located
in indoor and outdoor environments
DTM
COMPONENT SPECIFICATIONS
Storage ambient temp. range
.......
-40°C (-40°F) to 105
o
C (221
o
F)
Operating ambient temp. range
.
-40°C (-40°F) to 100°C (212°F)
1
Terminal connections
........................
up to 2.5 mm
2
(28-12 Awg)
Maximum RTD capacity
.............................................................. 6
1. For designs that allow operation in ambient conditions below -40°F (-40°C) contact Thermon..
DTM
CONNECTION DIAGRAM
CANBus & Power
Connector
LED Identifier To
Address Each DTM And
Each Of 6 RTD Sensors
LED Identifier To
Address Configurable
Input/Output Channels
RTD Inputs
DTM
DIMENSIONAL DATA
41 mm
(1-5/8")
111 mm
(4-3/8")
77 mm
(3")
IOM
(INPUT OUTPUT MODULE)
The IOM is a DIN rail mountable input/output module with
6 individually configurable input/output channels and one
dedicated system fault alarm output. Outputs may be configured
to signal a variety of conditions such as trips, low temperature
alarms, ground/earth leakage alarms, etc. Inputs may be used to
trigger a variety of events such as load shed or forcing on circuits.
IOM
DIMENSIONAL DATA
IOM
PRODUCT FEATURES
• Operates in a wide range of ambient conditions
• DIN rail mountable
• Conformal coated printed circuit board for use in panels located
in indoor and outdoor environments
IOM
COMPONENT SPECIFICATIONS
Storage ambient temp. range
.......
-40°C (-40°F) to 105
o
C (221
o
F)
Operating ambient temp. range
.
-40°C (-40°F) to 100°C (212°F)
1
Terminal connections
........................
up to 2.5 mm
2
(28-12 Awg)
IOM
CONNECTION DIAGRAM
41 mm
(1-5/8")
111 mm
(4-3/8")
77 mm
(3")
CANBus & Power
Connector
Alarm Relay
Outputs
SPECIFICATION GUIDE
5
THERMON.COM