35
Dec
Hex
Add CKT# x 100 to Base Memory Location to get the MODBUS Data Address
(Values offset from the CANBus memory map by -80 eg alarms in CANBus is memory location 185, in Modbus is 185)
4
100
0x064
Control Temperature for the DCM
RTD Reading for the DTM
Value x10
This location on the DCM is the temperature that it has decide to
control off.
This location on the DTM is an RTD reading.
4
101
0x065
Which DTM and RTD that the circuit is
controlling from
low Byte = DTM address 1-199
High Byte = RTD from DTM 1-6
4
102
0x066
Heater Current
Value x 10 (A)
4
103
0x067
Ground Current
Value in (ma)
4
104
0x068
Heater Percent On
Range = 0-100%
4
105
0x069
Alarms
Bit definitions
0x8000(bit) High Current Trip
0x4000(bit) Programing error
0x2000(bit) Current over .5A when circuit off
0x1000(bit High Ground Trip bit
0x0800(bit) RTD Fault No Communication for
all assigned RTD's
0x0400(bit) High Temperature trip
0x0200(bit) RTD Fault ( all assigned RTD's in
fault)
0x0100(bit) Not Used
0x0080(bit) High Current
0x0040(bit) Low Current
0x0020(bit) Circuit Fault
0x0010(bit) High ground current
0x0008(bit) RTD Fault No Communication
0x0004(bit) High temperature Alarm
0x0002(bit) RTD Fault (one or more assigned RTD's in fault)
0x0001(bit) Low temperature Alarm
4
109
0x06D
RTD 1 Temperature Reading
Value x10
4
113
0x071
RTD 2 Temperature Reading
Value x10
4
117
0x075
RTD 3 Temperature Reading
Value x10
...
4
185
0x0B9
RTD 20 Temperature Reading
Value x10
Cable Type
Recommended
120 ohm, -20°C to +60°C (-4°F to +140°F)
22AWG FHDPE insulation PVC outer jacket
Belden 3107A or equal
120 ohm, -30°C to +80°C (+22°F to +176°F)
24AWG PE insulation PVC outer jacket
Belden 9842 or equal
120 ohm, +70°C to +200°C (+94°F to +392°F)
24AWG Teflon FEP insulation, Teflon FEP outer jacket
Belden 89842 or equal
Appendix E: Recommended Wiring For RS 485 Communications