LevelPRO Specific Parameters
Parameter
Tab
Type R/W Description
Set up alarm triggering point, clear point, and gauge actions when
alarm happens for ALARM1.
ALARM1
Others ALM
R/W
Sub-parameter
Description
ACTION
Select the action used to indicate that the alarm
has been triggered.
- Nothing
- Control relay 1/2
- Output 1 to FAULT LOW
- Output 1 to FAULT HIGH
SET_POINT
The process level at which the alarm will
activate
CLR_MODE
Select a clear point (clr point) or dead band
(deadband) to clear the alarm.
CLR_POINT_
DEADBAND
Enter clear point or dead band value.
Set up alarm triggering point, clear point, and gauge actions when
alarm happens for ALARM2.
ALARM2
Others ALM
R/W
Sub-parameter
Description
ACTION
Select the action used to indicate that the alarm
has been triggered.
- Nothing
- Control relay 1/2
- Output 1 to FAULT LOW
- Output 1 to FAULT HIGH
SET_POINT
The process level at which the alarm will
activate
CLR_MODE
Select a clear point (clr point) or dead band
(deadband) to clear the alarm.
CLR_POINT_
DEADBAND
Enter clear point or dead band value.
C-4
LevelPRO with
F
OUNDATION
™ fieldbus
Application Guide
Thermo Fisher Scientific
Содержание LevelPRO Series
Страница 2: ......
Страница 3: ...LevelPRO With FOUNDATION TM Fieldbus Application Guide P N 717915 Revision A ...
Страница 4: ......
Страница 6: ...This page intentionally left blank ...
Страница 8: ...This page intentionally left blank ...
Страница 54: ...This page intentionally left blank ...
Страница 64: ...This page intentionally left blank ...
Страница 70: ...This page intentionally left blank ...
Страница 94: ...This page intentionally left blank ...
Страница 98: ...This page intentionally left blank ...