Chapter 6
Diagnostics
This chapter provides on the Diag/Service menu in the NI-FBUS
Configurator root menu. The Diag/Service menu provides access to the
Loop Test, Trim Analog Output, and Alarm Bad Flags Status items.
Note
If you are not using the NI-FBUS Configurator, reference the
documentation that came with your host system.
▲
Loop Test
The Loop Test function allows you to manually manipulate the analog
output to a selected constant output value.
1.
In the NI-FBUS Configurator, go to
AI_TRANSDUCER > Root
Menu > Diag/Service > 1 Loop Test > Loop test
.
2.
The first loop test screen appears. Click
Next
when you are ready to
continue.
Figure 6–1.
Initial loop test screen
Thermo Fisher Scientific
LevelPRO with
F
OUNDATION
™ fieldbus
Application Guide
6-1