Sarasota 2000 Ultrasonic Multipath
Flowmeter
Appendix 1 SCREEN FLOW DIAGRAMS, Page A1-14
Thermo Fisher Scientific
APPENDIX 1 LCD SCREENS
SCREEN S11: POWER RAILS (RESULTS)
(Screen accessed via S1:Station Diagnostics)
S11 POWER RAILS
CPU Power: 5.05 Volts
Main Power: 15.24 Volts
Backup Power: 11.85 Volts
Clock Battery: ok
Station
POWER RAILS
•
Typical value - CPU:
5 Volts +/- 0.2
•
Typical value - Main:
AC powered 14 to 16 Volts. DC powered as back-up
•
Typical value - Back up: 11.5 to 14 Volts
•
Clock
battery can be ‘ok’ or ‘replace’
SCREEN S12: SOFTWARE VERSION (RESULTS)
(Screen accessed via S1:Station Diagnostics)
S12 Softwar e Version
Boot Rom : 2.1
CPU Card : 2.1
Card
2
:
2.0
Card
3
:
2.0
Card 4 : 2.0
Card 5 : 2.0
Card 6 : 2.0
Card 7 : 2.0
SOFTWARE VERSION
•
The card numbers are addresses, not positions in the rack.
•
Addresses are set by jumper links on the cards, see Section 2.3
•
See Appendix 5: Site Data for relation between card type/address/position as
supplied.