Sarasota 2000 Ultrasonic Multipath
Flowmeter
Section 2, SYSTEM COMPONENTS, Page 2-7
Thermo Fisher Scientific
SYSTEM COMPONENTS
2.3.3 Optional
items
The flowmeter enclosure also houses an optional number of the following cards:
•
Transducer interface cards (TIFs) (up to 4 may be fitted).
•
I/O card (none, 1 or 2 may be fitted)
•
Relay (VFC) card (none or 1 may be fitted)
Details are given in Appendix 3: Specification section, but in summary:
2.3.3.1
Transducer interface card (TIF)
Fig 4 Transducer Interface Card (TIF)
The flowmeter has capacity for up to four TIFs as standard. Each one is capable of being
connected to 2 velocity paths (4 transducers) directly or 8 paths (16 transducers) by multi-
drop, and 1 ultrasonic depth transducer directly or 4 by multi-drop. Each TIF must have its
address set via the jumper links PL7 shown in the diagram above. The addresses are in the
form of a binary code with the least significant digit at the top of PL7. No link for 0; link present
for 1.
TIF1, card position 9, address 4, PL7 Links 0100
TIF2, card position 8, address 5, PL7 Links 0101
TIF3, card position 7, address 6, PL7 Links 0110
TIF4, card position 6, address 7, PL7 Links 0111
When setting up the flowmeter, the cards and their addresses are programmed via the
keyboard and screens as described in Appendix 1: LCD Screens or via GAFA as described in
Appendix 2: GAFA Screens. When a TIF is changed during service, the replacement must
have the same address set.