72
Activation
Description
Powerup
Press and hold the program button while switching on the bus voltage.
5.5 Operation mode
The PresenceLight 180x-KNX and PresenceLightx-360 KNX have 3 operation modes:
●
Normal
●
Test presence (page 75)
●
Test light (page 77)
5.6 Switch-on behaviour
After every time the bus voltage is switched or the parameters are downloaded by
ETS, the detector runs through its start-up phase (indicated by LED).
1. Start-up phase (30 seconds)
●
LED blinks once per second
●
Switching: outlet light receives an ON telegram irrespective of brightness
●
Constant light control: control is inactive, lighting is maximum dimmed (Value
telegram 100 %).
●
If there is no presence or sufficient brightness, an OFF telegram is sent after
30 sec. (Light off).
2. Operation mode normal
●
The detector is ready for use (LED off)
3. Event of malfunction
●
LED flashes rapidly
●
Troubleshooting see page 80