4 Transmitter
16
With the alarm definition, however, the physical measuring
range limits are decisive.
Measuring
range/standard scaling
Maximum scaling
0 to 50 Pa
-5 to 15 Pa
0 to 50 Pa
-25 to 75 Pa
0 to 100 Pa
-50 to 150 Pa
0 to 500 Pa
-250 to 750 Pa
0 to 10 hPa
-5 to 15 hPa
-10 to 10 Pa
-20 to 20 Pa
-50 to 50 Pa
-100 to 100 Pa
-100 to 100 Pa
-200 to 200 Pa
-500 to 500 Pa
-1000 to 1000
-10 to 10 hPa
-20 to 20 hPa
4.2.8.
Alarm handling
For upper and lower alarm limits, individual alarms as well as
collective alarms can be specified. If the collective alarm function is
activated, an alarm is triggered as soon as the alarm limit of an
alarm is exceeded, if this alarm is assigned to the collective alarm.
The testo 6383 monitors limit values with the help of relays. If a
reading is outside the limit values, a relay to be specified by the
user is switched.
If the reading reverts to more than a specified hysteresis below or
above the limit value, the alarm is cancelled.
In addition, information about the occurrence of error/status
messages can be provided by means of a collective alarm relay,
see Status, warning and error messages, page 50
If multiple alarm messages are activated at the same time,
the last alarm is shown. If the alarm is cancelled again, the
previous messages are no longer shown.