Tilt and remove the stationary contact as shown in Fig. 80. (The insulation sheet will be removed at the same time.) If the
current sensor and power supply CT hinder the removal of the stationary contact, make a record of the ties for control wires
between the current sensor and power supply CT (position/number of ties and type of control wires) using a digital camera, then
cut the ties and remove the stationary contact. Restore the ties after replacing the stationary contact.
Ties: TYTON Insulok T18RHS (heat resistance grade: HS, 100 mm long x 2.5 mm wide) or equivalent (2 or 3 pcs per pole)
Fig. 80 Removing the stationary contact
5) Reinstall each part or component in reverse order of removal after inspection. Make sure the insulation sheet is installed. Be sure
to restore the ties if they have been cut during removal of the stationary contact.
6) After installing the moving and/or stationary contact, be sure to perform 10 - 20 cycles of open/close operation and then
retighten the contact mounting screws to the specified torque.
Fig. 81 shows the contacts in closed and open state.
Open state
Closed state
Fig. 81 State of contacts
Opening distance
measuring points
Current sensor
Control wire
N-phase unit is marked
with "N" in this area.
Stationary contact
Stationary arcing contact
Stationary contact
(tilted)
Insulation sheet
Power supply CT
Stationary contact
(removed)