3. GENERAL
3-1. Types and Descriptions
TemPower2
is available in types shown in Tables 3 and 4.
Table 3-1 Standard types
Frame size (A)
800
1250
1600
2000
2500
3200
4000
4000
Type
AR208S
AR212S
AR216S
AR220S
AR325S
AR332S
AR440SB
AR440S
Max. rated current [
I
n
] (A) *1, *2
IEC, EN, AS
800
1250
1600
2000
2500
3200
4000
4000
JIS
Marine use
N-phase rated current (A)
800
1250
1600
2000
2500
3200
4000
4000
Number of poles *3, *4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
Dielectric withstand voltage [
U
i
] (50/60Hz) *5
1000
1000
1000
1000
1000
1000
1000
1000
Operating voltage [
U
e
] (50/60Hz) *6
690
690
690
690
690
690
690
690
Rated breaking/making current [kA sym rms/kA peak]
IEC ,EN, AS [
I
CS
=
I
CU
]
JIS C 8201-2-1 Ann.1 Ann.2
AC 690V *8
50/105
65/143
85/187
75/165
AC 440V
65/143 *10
85/187 *10
100/220
100/220
NK *7
AC 690V
50/115
65/153
*14
75/179
AC 450V
65/153 *10
85/201 *10
*14
100/245
For DC
DC 250V *9
40/40
Rated short-time current [
I
CW
] [kA rms] (1 sec.)
65
85
100
100
Rated latching current (kA)
65
85
85
100
Endurance
in number of ON-
OFF cycles *11
Mechanical
With maintenance
30000
30000
30000
25000
20000
20000
15000
15000
Without maintenance
15000
15000
15000
12000
10000
10000
8000
8000
Electrical
Without
mainte-
nance
AC 460V
12000
12000
12000
10000
7000
7000
3000
3000
AC 690V
10000
10000
10000
7000
5000
5000
2500
2500
Installation
Draw-out or fixed type
Mass (kg) for draw-out type
73
86
73
86
76
90
79
94
105
125
105
125
126
158
139
176
External dimensions (mm)
Fixed
type
*12
a
360
445
360
445
360
445
360
445
466
586
466
586
-
-
-
-
b
460
-
-
c
290
-
-
d
75
-
-
Draw-
out type
*13
a
354
439
354
439
354
439
354
439
460
580
460
580
460
580
631
801
b
460
460
460
c
345
345
375
d
40
140
53
Connection method
Line side
Vertical, horizontal or front terminals
Vertical terminals
Vertical terminals
Load side
Vertical, horizontal or front terminals
Vertical terminals
Vertical terminals
Control circuit terminal type
screw terminals
Spring charging method
Manual or motor charging
Overcurrent release (OCR)
No OCR, or L-characteristic for general feeder protection (In case of AGR-11B)
No OCR, L-characteristic for general feeder protection, R-characteristic for general feeder protection or S-characteristic for
generator protection (In case of AGR-21B,22B,31B)
Operation indication
Group indication (In case of AGR-11B)
Individual indication (In case of AGR-21B,22B,31B)
Tripping device
Tripping coil
(TC)
Standard equipment for OCR-equipped ACB
Shunt trip device
(SHT)
Optional
undervoltage trip
device (UVT)
Optional
Auxiliary switches
Number of switches
4C (standard), 7C or 10C; available for general feeder or microload
Terminal type
screw terminals
Operation power *15
Rated voltage
AC100V, AC110V, AC120V, AC200V, AC220V, AC240V,
DC24V, DC48V, DC100V, DC110V, DC125V, DC200V or DC220V
*1: Ambient temperature: 40°C (45°C for marine used)
)
*2: With horizontal terminals for AR208S - 216S and vertical terminals for AR220S - 440S
*3: For 2-pole applications, use two poles at both ends.
*4: 4-pole ACBs are not applicable to power distribution IT systems unless N-phase protection is provided.
*5: Varies depending on applicable standards. AC1000V applies to ACBs conforming to IEC60947-2 and JIS C8201-2.
*6: Varies depending on applicable standards. AC690V applies to ACBs conforming to IEC60947-2 and JIS C8201-2.
*7: Applicable to 3-pole ACBs with INST or MCR.
*8: For applicability to power distribution IT systems, consult us
*9: A special version of the breaker is available to use above 250V DC. Contact Terasaki for details.
*10: For AC500V
*11: Expected service life based on endurance test. The service life of ACB depends on the working and environmental conditions. Refer to chapter 6
“Maintenance, Inspection and
Parts Replacement
”.
*12: For both vertical and horizontal terminals
*13: This manual covers draw-out type ACBs.
*14: In applying or going to apply.
*15:
For more information, please refer to page 23 and 25.