Table 6 shows the dielectric withstand voltage and the insulation resistance of the ACBs.
CAUTION
Do not perform dielectric withstand/insulation resistance tests under other conditions than specified. Doing so may cause a
malfunction.
Table 6 Dielectric withstand voltage and insulation resistance
Circuit
Dielectric withstand voltage (50/60Hz)
Impulse withstand
voltage
U
imp
Insulation
resistance
(DC500V Megger
used)
Main circuit
Between poles, and terminal group and ground
AC3500V
1 minute
12kV
300M
Control circuit
Auxiliary
switches
For general feeder
Between terminal group and ground
AC2500V
1 minute
6kV
100M
For microload
Between terminal group and ground
AC2000V
1 minute
4kV
100M
Position switches
Between terminal group and ground
AC2000V
1 minute
4kV
100M
Overcurrent release
Between terminal group and ground
AC2000V
1 minute
4kV
100M
Undervoltage trip device,
Reverse power trip device
Between terminal group and ground
AC2500V
1 minute
6kV
100M
Other accessories
Between terminal group and ground
AC2000V
1 minute
4kV
100M
The above data applies to new ACBs. Device terminals within ACBs are not covered. Use a DC500V Megger to measure the insulation resistance.
Table 7 shows the internal resistance and power consumption of the ACBs.
Table 7 Internal resistance and power consumption
Type
AR208S
AR208D
AR212S
AR212D
AR216S
AR216D
AR220S
AR325S
AR332S
AR440SB
AR440S
Frame size (A)
800
1250
1600
2000
2500
3200
4000
4000
DC internal resistance (m
) (for 1-pole ACB)
0.033
0.033
0.028
0.024
0.014
0.014
0.017
0.014
AC power consumption (W) (for 3-pole ACB)
200
350
350
490
600
780
1650
1060
Type
AR212H
AR216H
AR220H
AR316H
AR320H
AR325H
AR332H
AR420H
AR440H
Frame size (A)
1250
1600
2000
1600
2000
2500
3200
2000
4000
DC internal resistance (m
) (for 1-pole ACB)
0.024
0.024
0.024
0.014
0.014
0.014
0.014
0.014
0.014
AC power consumption (W) (for 3-pole ACB)
260
350
490
310
430
600
780
*1
1060
*1:Contact us.
Table 8 shows applicable current of the ACBs. The applicable current varies depending on the ambient temperatures.
Table 8 Dependence of applicable current on ambient temperature
Type
AR208S
AR208D
AR212S
AR212D
AR216S
AR216D
AR220S
AR325S
AR332S
AR440SB
AR440S
Standard
Conductor size
Ambient
temperature (°C)
2 × 50 × 5t
2 × 80 × 5t
2 × 100 × 5t 3 × 100 × 5t 2 × 100 × 10t 3 × 100 × 10t 4 × 150 × 10t 4 × 150 × 6t
IEC60947-2
EN60947-2
AS3947-2
JIS C8201-2-1
Ann.1 Ann.2
40 (standard ambient
temperature)
800
1250
1600
2000
2500
3200
4000
4000
45
800
1250
1600
2000
2500
3200
4000
4000
50
800
1250
1600
2000
2500
3200
3940
4000
55
800
1200
1540
1820
2500
2990
3820
3940
60
800
1150
1460
1740
2400
2850
3690
3760
NEMA,SG-3
ANSI C37.13
40 (standard ambient
temperature)
800
1250
1540
2000
2500
3200
3310
3700
45
800
1190
1470
1960
2500
3010
3200
3580
50
800
1130
1390
1860
2440
2860
3100
3470
55
790
1070
1310
1750
2300
2690
2980
3350
60
740
1000
1230
1640
2150
2520
2870
3140
JEC-160
40 (standard ambient
temperature)
800
1100
1460
1740
2370
2610
2870
3230
45
800
1060
1400
1680
2280
2510
2750
3100
50
800
1010
1340
1600
2180
2400
2620
2970
55
770
960
1280
1530
2080
2290
2490
2830
60
730
920
1220
1450
1970
2170
2360
2690
Type
AR212H
AR216H
AR220H
AR316H
AR320H
AR325H
AR332H
AR420H
AR440H
Standard
Conductor size
Ambient
temperature (°C)
2 × 80 × 5t
2 × 100 × 5t 3 × 100 × 5t 2 × 100 × 5t
3 × 100 × 5t 2 × 100 × 10t 3 × 100 × 10t 2 × 150 × 6t
4 × 150 × 6t
IEC60947-2
EN60947-2
AS3947-2
JIS C8201-2-1
Ann.1 Ann.2
40 (standard ambient
temperature)
1250
1600
2000
1600
2000
2500
3200
2000
4000
45
1250
1600
2000
1600
2000
2500
3200
2000
4000
50
1250
1600
2000
1600
2000
2500
3200
2000
4000
55
1250
1600
1820
1600
2000
2500
2990
2000
3940
60
1250
1550
1740
1600
2000
2400
2850
2000
3760
NEMA,SG-3
ANSI C37.13
40 (standard ambient
temperature)
1250
1600
2000
1600
2000
2500
3200
*1
3700
45
1250
1600
1960
1600
2000
2500
3010
*1
3580
50
1250
1600
1860
1600
2000
2440
2860
*1
3470
55
1250
1510
1750
1600
1950
2300
2690
*1
3350
60
1240
1420
1640
1550
1830
2150
2520
*1
3140
JEC-160
40 (standard ambient
temperature)
1250
1500
1740
1600
2000
2370
2610
*1
3230
45
1250
1440
1680
1600
2000
2280
2510
*1
3100
50
1250
1380
1600
1600
2000
2180
2400
*1
2970
55
1250
1310
1530
1600
1920
2080
2290
*1
2830
60
1230
1250
1450
1600
1820
1970
2170
*1
2690
*1:Contact us.
Notes: For AR208S, AR212S, AR216S, AR208D, AR212D and AR216D it is assumed that main circuit terminals are of horizontal type at both the line and load sides. For other
types, it is assumed that main circuit terminals are of vertical type at both the line and load sides. The above values may vary depending on the switchboard configuration.