Fig. 101 Remedial actions against a symptom of "closing impossible"
The ACB cannot be closed.
Does the operation
mechanism work well?
No
Are closing springs
charged?
Yes
Is the ACB body in an
intermediate position?
No
Is the OFF button
locked or any other OFF-
lock active?
No
Is the SHT trip
command active?
No
Check the UVT
attraction voltage.
OK
Check SHT,
MHT and UVT. See Nos.
2, 18 and 20 in Table
43.
OK
Check the operation
mechanism. See No. 12
In Table 42.
OK
Is manual closing
possible?
Yes
Yes
No
Yes
Yes
Yes
NG
NG
NG
No
Is manual closing
possible?
No
Charge
Move the body to the “CONN.”,
“TEST” or “ISOLATED” position.
Unlock
Deactivate
Supply correct voltage.
Repair/replace
Repair
Contact Terasaki.
Yes
Do operation indication
contacts work well?
No
Check
contacts. See Nos.
9 - 10 in Table 42 and Nos.
6 - 7 in Table
43.
OK
Check the operation
mechanism. See No. 12
in Table 42.
OK
Is manual closing
Possible?
Yes
Check the operation voltage.
OK
Check
the control circuit
and terminals. See Nos.
5 and 11 in Table
42.
OK
Check LRC. See Nos.
9 - 13 in Table 43.
OK
Is electrical closing
possible?
No
Contact Terasaki.
Yes
NG
NG
No
NG
NG
NG
Yes
Check downstream
circuits.
Repair/replace
Repair
Contact Terasaki.
Supply correct voltage.
Repair
Repair/replace
End