KRB-5404
108
1
Repeat steps 1 to 5 for the wire on the
other end of the cable.
Temporarily tighten the cable
fixing nut.
Holding the wire, tighten the
Wire fixing nut to a torque of
4.7 to 5.9 N.m.
Push in and hold the wire until
It stops against the groove end
of the level.
Loosen the cable fixing nut and the wire fixing nut.
Attach the cable in the cable mounting
Hole and insert the wire into the wire
Insertion hole of the wire fixing bolt.
6
Make sure the distance between the support and the lever is
as specfied and then tighten the cable fixing nut to a torque
of 12.5N.m. If the distance is out of the specfied range,
proceed to step 8 to adjust the distance.
3
5
4
7
If the ACBs are of a draw-out type, insert the ACB bodies into the
chassis to the connected position. Do not turn the ACB(s) on
until it is in the connected position. If the ACB is a fixed typed,
unlock the ACB.
After making sure the main circuit is not energised, check the
operation of the ACB(s). Do not touch the interlock during
operation.
8
9
10
Cable
Sleeve
Cable fixing nut
Wire
2
If the distance is too small, turn the cable-fixing nut counter
clockwise to lower the sleeve and the lever, increasing the
distance until it falls within the specified range. If the
distance is too large, turn the cable-fixing nut clockwise to
raise the sleeve and the lever