Alarm
Code
Displayed message
Reset
Delay
Relè
Action
ALP01
Position: ID1 Flowmeter water
geothermal circ.
After 5 times per
hours it becomes
manual
At starting: 15s (par.
Hc15) at regime: 5s
(par. Hc16)
Yes
Stop the machine when the maximum time
is reached
ALP02
Position : ID4 Thermal pumps
Manual
Immediate
Yes
Stop the machine
ALP03
Position: ID10 Flowmeter water primary
circuit
After 5 times per
hours it becomes
manual
At starting: 15s (par.
Hc12) at regime: 5s
(par. Hc13)
Yes
Stop the machine when the maximum time
is reached
ALP04
Position: ID5 Thermal solar pump circuit
Manual
Immediate
Enabled (Gfc01)
Stop the pump of the solar collector
ALR01
Position: ID7 Alarm boiler/ resistance
integr. system
Automatic
Immediate
Enabled (Gfc02)
Stop boiler/resistance operation primary
circuit integration
ALR02
Position: ID6 Thermal boiler/resistance
DHW from digital input
Manual
Immediate
Settable
(Gfc03)
Stop the boiler/resistance integration DHW
ALF01
Position: ID1 Thermal fan
Manual
Immediate
Stop the machine
ALT01
Threshold reached worked hors
compressor 1
Manual
Immediate
Settable
(Gfa01)
Just reporting
ALT02
Threshold reached worked hors
compressor 2
Manual
Immediate
Settable
(Gfa01)
Just reporting
ALT03
Threshold reached worked hors
geothermal pump
Manual
Immediate
Settable
(Gfa01)
Just reporting
ALT04
Threshold reached worked hors
primary circ.
Manual
Immediate
Settable
(Gfa01)
Just reporting
ALT05
Threshold reached worked hors
DHW pump
Manual
Immediate
Settable
(Gfa01)
Just reporting
ALT07
Threshold reached worked hors
solar pump
Manual
Immediate
Settable
(Gfa01)
Just reporting
ALT08
Threshold reached worked hors
internal battery fan
Manual
Immediate
Settable
(Gfa01)
Just reporting
ALU01
Antifreeze geothermal exchanger
Manual (par. Gfc28) Immediate
Yes
Stop the machine
ALU02
Antifreeze primary exchanger
Manual (par. Gfc32) Immediate
Yes
Stop the machine
ALU03
Overheating system exchanger
Manual
Immediate
Yes
Stop the machine
ALW01
Reached threshold high domestic
temperature
Automatic
60 sec
Enabled (Gfc01)
Just reporting
ALW02
Reached threshold of max domestic
temperature to the solar collector
Automatic
60 sec
Yes
Just reporting
ALW03
Exceed max. time for defrosting end
Automatic
Immediate
Yes
Just reporting
ALD01
Alarm EEPROM
Manual
Immediate
Yes
Stop the machine
ALD02
Sensor EVD EVO broken or disconnected
Automatic
Immediate
Yes
Stop the machine
ALD03
Error engine EEV
Manual
Immediate
Yes
Stop the machine
ALD04
Low overheating (LowSH)
Manual
Immediate
Yes
Stop the machine
ALD05
Low suction temperature
Manual
Immediate
Yes
Stop the machine
ALD06
Low evaporation temperature (LOP)
Manual
Immediate
Yes
Stop the machine
ALD07
High evaporation temperature (MOP)
Manual
Immediate
Yes
Stop the machine
ALD08
High condensation temperature (HiTcond) Manual
Immediate
Yes
Stop the machine
ALD09
Driver offline
Automatic
Immediate
Yes
Stop the machine
ALL01
Device Power+ n. 1 Offline
Automatic
30 sec
Yes
Stop the machine
ALL02
Alarms Power+ n.1
0: No error
1: Overcurrent
2: Engine overload
3: Overtension
4: Undertension
5: Overtemperature
6: Undertemperature
7: Overcurrent HW
8: Overtemp. engine
9: Reserved
10: Error Cpu
11: Param. default
12: Ondulation DC bus
13: timeout com.ser.
14: Error thermistor
15: Error Autotuning
16: Drive disabled
17: Missing motor phase
18: Failed fan
19: Stalling engine
Manual
Immediate
Yes
Stop the machine