11 Initial operation
The start up of the system has to be made by a competent staff
that received a specific training. After the correct hydraulic
and electric installation of the heat pump (HP), as specified in
previous pages, you have to proceed as following.
11.1 Preliminary checks
Make sure that power supply cables of HP have a suitable section
as shown in the installer guide, on the base of the power used
and the lenght of the cables and that siano stati inseriti suitable
protection devices have been inserted. In the same way the
signal cables have to have the features required.
Control that Y filter is correctly connected in the return pipe of
HP so to avoid obstructions or malfunction of the heat plate
exchanger.
After you checked the points mentioned above you can proceed
with the ignition of the machine.
NOTE!
Pay attention after supplying the HP it will activate the authomatic
function of oil heating (the duration depends from the necessary
time to bring to temperature the oil contained in the compressor,
then depending on the starting temperature).
11.2 Testing and startup
•
Access to menù “Assistance”: PRG --˃ G. Assistance --˃ g.
Manual management --˃ SERVICE PASSWORD
Flow check:
•
Screen Gg01
N04: Pump primary, set up on
manual function “MAN”.
Verify the correct circulation of water in the circuit. If after
5 attempts of ignition the circulator doesn’t have the right
flow, the red light turn on on the control panel, and it is
necessary to check the effective opening of the hydraulic
circuit (portcullis), the presence of air in the system or
clogging in the Y filter and provide to remove them.
•
Screen Gg01
N04: Pump primary, set up on
authomatic function “AUT”
Vent valves , monoblock version.
Vent valves , split version.
Running of the compressor:
Every HP is tested in the company before the supply, but we suggest
in any case to make a short running in, so not to solicitate overly
the new compressor. In this regard we suggest to let in manual the
rps compressor at a medium value (50-60 rps) for one/two hours at
least.
•
Access to menu “Assistance”: PRG --˃ G. Assistance --˃ g.
Manual management --˃ SERVICE PASSWORD