Example 2 condensate drain
•
Example 3 condensate drain with condensate drain element
The condensation water accumulated during the operation must be
carried away without it can freeze. To ensure the correct outflow the
heat pump must be in a horizontal position. The condensation water
pipe must have a minimum diametre of 18mm and must flow in the
drain channel without it can freeze. Don’t discharge the condensate
directly into purification basins and moats. The aggressive fumes
and the condensation pipe, if it isn’t protected against frost, can
cause irreparable damages to the evaporator.
In places where there are snowfalls, install the heat pump at least 25
cm from the floor to avoid clogging in the suction and condensate
drain area.
•
Preparation of the base for condensate drain
•
Example 1 condensate drain (it is advisable inter the
condensate drain pipe to avoid ice if you don’t buy the
optional
heating element for the condensate drain).
Frost proof
depth
min 200mm
Frost
proof
depth
Frost proof
depth
min 200mm
Frost
proof
depth
Frost proof
depth
min 200mm
Frost
proof
depth