51
Partition
: in this section you can configure the partition number you wish to assign to the given
event. The default configuration for partition is 01.
Zone
: in this section you can configure the zone number you wish to assign to the given event.
The default configuration for zones is in accordance with the number of the inputs (001 to 006).
Notification template
: in this section you can select a preconfigured notification template which
you want to use for the given event. If you want to use additional notification templates, these
should be added prior to configuring the events. If you do not want to send a report to CMS on the
given event, select the template named “
EMPTY
”.
Output
:
In this section you can configure the output(s) to be controlled upon occurrence of a given input
event.
Output control mode
: in this section you can configure the control mode of the output (or the
selected output 1 or 2 in case of the IN4.R2 model). Available options:
None
: the output will not be used.
Monostable
: the output will be activated for the time configured in the
“Duration”
section
of the output parameter settings, then it will revert to normal state automatically.
The duration can be configured from 5 milliseconds to 60 minutes.
Bistable ON
: the output will be activated permanently and will change state only upon
receiving a different command or upon power loss.
Bistable OFF
: the output will become deactivated.
State change
: the output will change state (if deactivated, it will become activated and if
activated, it will become deactivated).
Pulse series
: the output can be controlled by pulse series as well. The number of pulse
series can be configured from 1 up to 3. For each pulse it can be configured how long the
output should be activated, how long should be deactivated, the number of repetitions and
the pause between repetitions. The active periods can be configured from 5 milliseconds to
60 minutes and the number of repetitions can be configured from 1 to 10, and the pause
between pulses can be configured from 5 milliseconds to 60 minutes too.
Output parameter settings
: this option becomes available if an output control mode is selected
which has further settings. In this section you can configure the additional settings of specific
output control modes, such as timings for monostable control and pulse series. Click on the “
Edit
”
button to open the parameter configuration window.
Voice call notification
:
In this section you can configure phone calls to be made when the given input event occurs.
The device will call the selected phone numbers and play the selected voice messages.
You can upload voice messages as audio files in the “
Voice messages
” menu.
Voice call
: in this section you can select the user phone numbers to which calls should be made.
The phone numbers should be configured in advance in the “
Reporting channels
” menu. Calls
will be made to the numbers enabled with the help of the checkboxes in the drop-down list.
Voice message
: in this section you can select the voice message which should be played in the
calls when the given event occurs. When receiving a call from the device, a built-in siren tone will
be played before each voice message. If a voice message has been configured for which no
message has been uploaded, the siren tone will be played continuously throughout the call.