7
2.4 Setting
parameters
To configure the settings select „
Parameter settings
” tab.
Functions of the upper 6 icons, respectively from left to right :
Read data from file
,
Save
data to file
,
Read data from module
,
Write data to module
,
Compare parameters
with module settings
and
Change password
. With these simple functions you can
easily save, load and archive the settings of the given module.
2.5 Customization of parameters
After selecting the „
Parameter Settings
” tab, zones, events, relay output, phone
numbers and other parameters can be set according to the instructions in the following
chapters.
2.5.1 Zone settings
Normally Open / Normally Close
: the active state of the zones can be set here
Normally Open: the input should be connected to „V-„ terminal to generate an event
Normally Close: the input should be connected by default to „V-„ terminal and then
interrupted to generate an event.
Zone sensitivity
: value selectable in tenth seconds, seconds or minutes, (0-254).
Shorter state changes on zone inputs are ignored by the module.
Entry delay
(value in seconds, 0-254):
This is the time available to disarm the module after violating the given zone. If
disarming is not performed till expiration, the alarm process starts.
Exit delay
(value in seconds, 0-254):
This is the period of time for which the module still ignores state changes of the given
zone after arming the system. (The period available for leaving the given zone).
24 hour zone
: change of zone state is transmitted by the module even if disarmed