Output zones configuration
The following functions are reserved to the Programmer.
Programming menu -> Configure -> Devices/Zones -> Output Zones
This function lets you link output modules to output zones.
Settings
Settings are described below.
Parameter
Description
Activations
Event type that activates the zone (Alarm, Pre-alarm Gas)
Silenceable
If
Yes
, the operator can deactivate the output module (i.e.: siren) by
entering a password.
If
No
, to deactivate the output, it is necessary to reset the panel.
Procedures
To create an output zone:
1. Select the
Add
option: a list of output zones in the system is displayed.
2. Select the first available output zone.
3. Set the required parameters:
4. Press
Next
to continue.
5. Select the loop that includes the output module to be linked.
6. Select the output module to be linked to the output zone.
7. Press
Save
to confirm.
To edit an output zone:
1. Select the
Edit
option: a list of output zones in the system is displayed.
2. Select the output zone to be edited.
3. Edit settings.
4. for parameter descriptions.
5. Press
Save
to confirm.
To delete an output zone:
1. Select the
Delete
option: a list of output zones in the system is displayed.
2. Select the output zone to be deleted
3. Press
Save
to delete the output zone.