ONEMINI
F
IRE
A
LARM
C
ONTROL
P
ANEL
U
SER AND
I
NSTALLATION
M
ANUAL
-
R
EV
.
1.0.3
/
2018
P
AGE
77
11.2
Enabling users and changing login codes
Only the Programmer operator can enable or disable user operator login. Each operator can
change their personal login code.
11.2.1
Programmer
Programming menu -> Configure -> Password
Procedures
To enable User login:
1. Set all Users who need to login to the unit to
Yes
.
2. Press
Save
to confirm.
To change the Programmer login code:
1. Select the
Change
option: the code change page is displayed.
2. Insert the new code.
3. Confirm the new code to save it.
11.3
Managing alarms
In case of alarm received from any device, the panel will activate immediately the internal
siren output and will turn on the red LED on the front panel.
The device in alarm status will turn on its red LED.
To avoid a loop overload, in case of more than one alarm, a maximum of 10 red
LEDs on the devices will be activated.
The following functions are reserved to the User