10.4.5
Set zone operating parameters
This function lets you set weekly zone behavior. This is helpful to bypass the unit on certain
days or at certain times.
Settings
Settings are described below.
Parameter
Description
Zone name
Name assigned to the zone
Weekly trend
Autoexclusio
n
Weekly trend linked to the zone.
(see
10.8.5 Setting weekly trends
).
protected
If set to Yes, you can set the times T1, T2, T2B and set the weekly survey of
trends.
T1
It is the warning phase; in the moment of its activation, the area is already in
alarm but the associated output are still not parties.
T2
And the investigation time to physically check the veracity alarm; T2B has the
same operation, but only if the warning comes from a button.
weekly trend
survey
By setting this parameter, you can program the zone protected or unprotected
during the week.
Procedure
1. Select the
Add
option: a list of zones in the system is displayed.
2. Select the required zone.
3. Select the
Settings
option.
4. Enter the required settings.
5. Press
Save
to confirm.
To verify that a zone is properly set as
protected
, also follow the following procedure:
1. Enter third level code 33333;
2. Select the Configure section;
3. Enter the System section;
4. Press the General Section;
5. Enter the Various section;
6. Verify that The terminals T1 and T2 are enabled; (Section 10.7.10 of this manual)
7. Perform the Log-Out;
8. Enter the second level code 22222;
9. Select the Maintenance section;
10. Select the Exclusions section;
11. Entering the section
protected
;
12. Verify that the area we have planned as
protected
is green