7.8
Power supply
7.8.1
Network input features
The control panel has to be installed according to the national installation standards.
It is requested to carry out a connection to a separated AC line that has to be marked with
the label
FIRE SYSTEM.
Use a double-pole switch minimum 6A.
The connection wires have to have a proper section area and a minimum insulation of
600V
.
The power supply input has to have the following features:
Supply voltage 230 Vac +/- 10%
Frequency 50/60 Hz
7.8.2
Grounding features
The grounding installation has to be carried out according to the CEI and ISPLES standards
and with a resistance lower than
10Ω
.
7.8.3
Panel power supply features
Following features are useful for the system installation:
Output operating voltage 27.6 V - Max. 500mA
Voltage of battery charger 27.6 V- Max. 900mA
Low battery threshold 21.6 Volts
Battery release threshold 20.4 Volts