10.4.6
Link an output module to a zone
This function lets you directly link output modules to a zone. When the zone is triggered, the
output modules automatically turn on.
Settings are described below.
Parameter
Description
Silenceable
If
Yes
, the operator can deactivate the output module (i.e.: siren) by
entering a password.
If
No
, to deactivate the output, it is necessary to reset the panel.
Procedures
To add a zone:
1. Select the
Add
option: a list of zones in the system is displayed.
2. Select the required zone.
3. Select the
Output Modules
option.
4. Select the output module loop.
5. Select the required module.
6. Set the required parameters:
7. Press
Save
to confirm.
To edit a zone:
1. Select the
Edit
option: a list of zones in the system is displayed.
2. Select the zone to be edited.
3. To edit linked events see
10.4.2 Link an event to a zone
for parameter descriptions.
4. To edit linked loops: see
10.4.3 Linking loops to zones
for parameter descriptions.
5. To edit linked devices see
10.4.4 Linking devices to zones
for parameter descriptions.
6. To edit operating parameters: see
10.4.5