Closed loop configuration
Below an example of closed loop configuration.
This type of configuration uses
L-
and
L+
FW
and
L-
and
L+
RET
It is possible to connect up to 240 detectors and I/O modules.
If SFx000E type sensors are used, install an insulator module or sensor/module
with on-board insulator for every 32 devices as required by current
specifications.
7.6.6
Connection requirements for a closed loop connection
Match the following requirements:
Total line length (between OUT and IN) should not exceed the maximum allowed
length according to the section of the cable used.
7.6.7
Connectable loop devices
It is possible to connect the following
Argus’s devices on the loop:
BS5000 (40900)
bases for SFx000 and SFx000E detector installation.
SF5100 (40910-8) optical smoke detector
SF5200 (40920-8) optical and rate of rise detector at 58 °C (class A1 and A1R)
SF5300 (40930-8) temperature detector, (class A1R and B)
SF5100E (IV100) (like SF5100 but without isolator)
SF5200E (IV200) (like SF5200 but without isolator)
SF5300E (LV350) (like SF5300 but without isolator)
Detector
Call point
L1+ AND
L1
– AND
L1 + RIT
L1
– RIT
Call point
Detector
Output
Module
Input
Module
Input
Module
Detector
Detector