Note:
To clear an anti-passback violation, the card must be used at another
appropriate reader to change the region number that the user is recorded
against.
Alternatively, anti-passback can be cleared for specific user(s) using the
Reset
anti-passback
button on the toolbar of the Users form. See the
CTPlus
Operators Manual
or CTPlus online help for more information.
Note:
The door must be opened after the reader is used before anti-passback
will take effect.
Note:
Anti-passback
settings do not apply to users with the “Privileged” flag in
regions 0 to 199.
Anti-passback
Select the type of anti-passback desired:
Disabled
– The anti-passback functionality is not active. The card will open
the door without generating an alarm.
Soft
– The card will open the door when used the second time but an
alarm will be generated.
Hard
– The card will not open the door when used a second time and the
attempt will generate an alarm.
Timed Hard
– The card will not open the door when used a second time in
succession at the same door within the programmed time and the attempt
will generate a report.
Anti-passback time
Enter the time delay that forces the user to wait until the delay timer expires.
Enter a number and specify
Sec
for seconds or
Min
for minutes.
Region IN
Specifies a region which represents the IN readers for each door.
When a valid card or PIN is entered at the door reader, the region that the user is
entering into is recorded against the user code. The system is then able to report
an anti-passback violation.
Select the region by clicking the
Browse
button, or type the region number
directly into the field.
Note:
The door must be opened for this to be effective.
Region OUT
Specifies a region which represents the OUT readers for each door.
When a valid card or PIN is entered at the door reader, the region that the user is
entering into is recorded against the user code. The system is then able to report
an anti-passback violation.