Programming general controller options
The NAC’s general controller options can be programmed on the
NAC options
tab of the DGPs form.
Each field is explained in the following sections.
Relay controllers
Enter a value in the range 1 to 8 in order to use TS0841 or TS0842 clocked relay
expansion cards. Alternatively, enter 0 (disabled) to use a TS0840 4-Way Relay
Card, or for no relay expansion.
Use a value that represents groups of eight clocked relays or open collectors. For
example:
Enter a value of 1 if one 8-way relay card is used (TS0841).
Enter a value of 2 if one 16-way open collector card is used (TS0842).
Enter a value of 4 if four 8-way relay cards are used (TS0841).
EOL resistor
The EOL (End-Of-Line) resistor is used to detect the electrical states of input
circuits. This field defines the actual resistor value.
Challenger
Plus
panels normally have the default 10 kΩ EOL resistor value to
detect the electrical states of the 16 input circuits connected directly to the
Challenger
Plus
panel. For systems that use a different EOL resistor, select the
required value from the list.
Input tamper monitoring
If the Challenger
Plus
panel monitors input circuits for tamper conditions, then the
NAC must do the same.