5-44
5-4-8 Original Home
Home routine is used to find and set a reference point for correct positioning.
To set a HOME reference position, one of input contacts ORG (external sensor input), CCWL, or CWL can be
used.
An encoder Z phase (marker pulse) can also be used as home reference and can be search by CW or CCW
direction. Following Home routine selections are available for setting parameter Pn 365.0.
Parameter Name Setting
Description
Control
Mode
0
Once the home routine is activated, motor will search for Home
Position switch in 1
st
preset speed in
CCW
direction
.
Input contacts CCWL or CWL can be used as the Home Reference
Switch.
Once Home reference switch is detected and complete, input contacts
CCWL
and
CWL
will act as limits input contact again.
Note:
When using this function, 1 or 2 setting of
Pn365.1
is not allowable.
Cn002.1 (
CCWL & CWL Input terminal function
) must to set as 0.
1
Once the home routine is activated, motor will search for Home
Position switch in 1
st
preset speed in
CW direction.
Input contacts CCWL or CWL can be used as the Home Reference
Switch.
Once Home reference switch is detected and complete, input contacts
CCWL
and
CWL
will act as limits input contact again.
Note:
When using this function, 1 or 2 setting of
Pn365.1
is not allowable.
Cn002.1 (
CCWL & CWL Input terminal function
) must to set as 0.
2
Once the home routine is activated , motor will search for Home
Position switch in 1
st
preset speed in
CCW direction
and sets the input
contact ORG (external sensor input) as a Home reference when ORG
contact is activated.
If
Pn365.1=2
, it will directly find the closest Rising-Edge of
ORG
to be the Home position (without a need for Home reference),then it
stops in accordance with
Pn365.3
setting.
3
Once the home routine is activated , motor will search for Home
Position switch in 1
st
preset speed in
CW direction
and sets the input
contact ORG (external sensor input) as a Home reference when ORG
contact is activated.
If
Pn365.1=2
, it will directly find the closest Rising-Edge of
ORG
to be the Home position (without a need for Home reference),then it
stops in accordance with
Pn365.3
setting.
4
Once the home routine is activated , motor will search for Home
position in 1st preset speed in
CCW
direction and sets the Home
reference
Servo drive start to find the Home position of the nearest Z phase.
(No need for Home reference)
When using this function, set
Pn365.1=2
.
After finished setting of
Z
Phase to the Home position, for the stop
method refer to the setting of
Pn365.3.
Pn365.0
On activation of
Home input
contact,
It sets the
search
direction
and Home
reference.
(Setting for
home routine)
5
Once the home routine is activated , motor will search for Home
position in 1st preset speed in
CW
direction and sets the Home
reference
Servo drive start to find the Home position of the nearest Z phase.
(No need for Home reference)
When using this function, set
Pn365.1=2
.
After finished setting of
Z
Phase to the Home position, for the stop
method refer to the setting of
Pn365.3.
Pi/Pe
Содержание TSTA Series
Страница 1: ......
Страница 12: ...1 6 1 4 2 Direction and Distance Fan Fan ...
Страница 15: ......
Страница 41: ...2 26 2 3 2 Position Control Mode Pe Mode Open Collector Pe mode External pulse positioning command ...
Страница 45: ......
Страница 59: ......
Страница 69: ......
Страница 175: ......
Страница 206: ...9 4 Dimension for TSTA 15 and TSTA 20 ...
Страница 207: ...9 5 Dimension for TSTA 30 ...
Страница 208: ...9 6 Dimension for TSTA 50 and TSTA 75 ...
Страница 211: ...DIMENSION TSB 07 08 SERIES 9 9 ...
Страница 214: ......
Страница 215: ......
Страница 218: ......